WATLOW Series 988 User’s Manual 2.13
Installation and Wiring, Chapter 2
Output 2 Wiring

Figure 2.13b — Switched DC, Open Collector

98 _ _ - _ _ _ C- _ _ _ _

Maximum voltage: 42VÎÎ(dc)
Maximum current: 1A 15 External
Load
+
16
17
-
COM

Figure 2.13d — 0-5VÎÎ, 1-5VÎÎand 0-10VÎÎ(dc) Process

98 _ _ - _ _ _ F- _ _ _ _

Minimum load impedance: 1K

Figure 2.13c — 0-20mA and 4-20mA Process

98 _ _ - _ _ _ F- _ _ _ _

Maximum load impedance: 800
15 +
-
17
16 +
-
17

Figure 2.13e — External Signal Conditioner Power Supply

98 _ _ - _ _ _ T- _ _ _ _ 15
16
1
2
+
-
+V
-V
Transmitter
4-20mA out
Input
1 or 2
-
+

Figure 2.13a — AC Outputs

Solid-state Relay
with
Contact Suppression

98 _ _ - _ _ _ B- _ _ _ _

0.5 amps, minimum off-state impedance: 20K
Electromechanical Relay
with
Contact Suppression
(Suppression between NO and COM contacts only)

98 _ _ - _ _ _ D- _ _ _ _

Form C, 5 amps, minimum off-state impedance: 20K
Electromechanical Relay
without
Contact Suppression

98 _ _ - _ _ _ E- _ _ _ _

Form C, 5 amps off-state impedance: 31M
Solid-state Relay
without
Contact Suppression

98 _ _ - _ _ _ K- _ _ _ _

0.5 amps, off-state impedance: 31M
External
Load
COM L1
L2
Fuse
NO
15
16
NC
17
(#17 for D & E outputs only)
+
Internal Circuitry
15
16
17
790
19 to 32VÎ (dc)
NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).
˜
NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter connect-
ed to input 1 or
input 2.
NOTE:
Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical
relay or solid state
relay output options
requires using an
R.C. suppressor.
Watlow carries the
R.C. suppressor
Quencharc brand
name, which is a
trademark of ITW
Paktron. Watlow
Part No. 0804-0147-
0000.
Loop powered