8
2.5 CONTROL AND ALARM OUTPUTS
32 Individually selectable control outputs:
Digital Outputs: Time proportioning, On/Off, Alarms: voltage
output: 5VDC at 6ma maximum for solid state or
other relays.
Analog: voltage or current: selectable (4 to 20ma, or 0 to 5
volts).
2.6 DIGITAL INPUT OR OUTPUT
24 DigitalOutputs: TTL Level: true= < 0.4v @ 6ma false = > 3.9v
@ 6ma
16 Digital Inputs: TTL Level:
2.7 ANALOG OUTPUTS
Types: 0 to 5Vdc at 5ma max.
4-20ma at 8Vdc max [maximum loop impedance
400 ohms].
Both are available at the output terminals of each
output. Either can be used -- no jumpers are
required. DO NOT USE BOTH ON SAME
OUTPUT.
Accuracy: +3%
Resolution: 0.4%
2.8 GENERAL
Power input: 120VAC, 60Hz , to power supply.
modules require 5vdc @ 5A max [6 slot].
Operating ambient: 0 to 50 C.
Humidity: 10% to 90%, non-condensing.
Enclosures: NEMA 4, 12, 13 and others optional.
Physical: 6 Slot Housing: 16.7" wide [19" standard rack
mount], 12.5" high, 7.5" deep.
3 Slot Housing: 10.7" wide.
Mounting: 4 mounting holes for standard rack or panel
mounting -- see outline drawings.
Weight: max imum 20 pounds depends on plug modules
selected.