• JIS and DIN curves
• Whole or tenth degree indication
• 150µA nominal RTD excitation current
Process
• Range selectable: 0-10VÎ(dc),0-5VÎ(dc),1-5VÎ(dc),0-20mA,4-20mA,
• Voltage input impedance 20kΩ
• Current input impedance 100Ω
• Minimum current source resistance 1MΩ
• Input resolution 50,000 bits (approx.) at full scale
• mV input impedance 20MΩ
Input 2 Event Input
• Contact or voltage
• 20KΩ input impedance
• Voltage input: event high state 3 to 36VÎ(dc), event low state 0 to 2VÎ(dc)
• Resistance/contact input:Ω event high state > 23kΩ, event low state 0 to 2k
Remote Set Point Input: mA or VDC Range Selectable
• Voltage input impedance 20kΩ
• Current input impedance 100Ω

Specifications

Controller

Microprocessor-based, user selectable control modes

Heat and cool auto-tune for control outputs

Universal input 1, auxiliary input 2, 4 outputs

Control outputs user selectable as on-off, P, PI, PID

Input sample period; Single input 10Hz (100 ms), dual input 5Hz (200 ms) adjustable digital filter

Display update; 2Hz (500 ms), adjustable digital filter

Output update; burst, 0.1 to 999.9 seconds

Input/Output/Communication isolation

Displayed in °C, °F, or process units

Operator Interface

Dual 4-digit LED displays: upper 10.2 mm (0.4 in.), lower 6.2 mm (0.244 in.)

Advance, Up Arrow, Down Arrow, Infinity tactile keys

Standard Conditions For Specifications

Ambient temperature 25°C/77°F ±3°C, rated line voltage, 50 to 60Hz, 0 to 90 percent RH non-condensing, 15 minute warm-up

Universal Input 1Thermocouple

Type J, K, T, N, C (W5), E, Pt 2, D (W3), B, R, S thermocouple types

>20MΩ input impedance

Maximum 20Ω source resistance

30µA open detection bias

RTD

• 2- or 3-wire platinum, 100Ω

Output TypesOpen Collector/Switched DC

• Open collector configuration: Maximum voltage 42VÎ(dc) Maximum current 200mA Ω Maximum “on” resistance 1.1 Maximum offstate leakage current 100µA

Switched dc configuration:

Switched dc supply voltage 22 to 28VÎ(dc) dc supply current limited to 30mA

Solid State Relay

Optically isolated

Zero cross switched

Without contact suppression

Minimum load current 0.5mA rms

Maximum current 0.5A rms at 20 to 280VÅ(ac)

Maximum offstate leakage current 10µA rms

For resistive loads only, must use RC suppression for inductive loads

Electromechanical Relay

Form C contact configuration

Minimum load current 10mA @ 5VÎ(dc)

Rated resistive and inductive loads: 2A @ 250VÅ(ac) or 30VÎ(dc) maximum

Electrical life 100,000 cycles at rated current

For resistive loads only, must use RC suppression for inductive loads

Process

Range selectable: 0-20mA, 4-20mA, 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)

Reverse or direct acting

0 to 10VÎ(dc) voltage output into 1000Ω minimum load resistance

0 to 20mA current output into 800Ω maximum load resistance

Resolution:

dc ranges = 2.5mV nominal mA ranges = 5µA nominal

Calibration accuracy: dc ranges = ±15mV mA ranges = ±30µA

Temperature stability 100ppm/°C

Retransmit

Range selectable: 0-20mA, 4-20mA, 0-5VÎ(dc), 1-5VÎ(dc), 0-10VÎ(dc)

0 to 10VÎ(dc) voltage output into a 1,000Ω minimum load resistance

0 to 20mA current output into an 800Ω maximum load resistance

Resolution:

dc ranges = 2.5mV nominal mA ranges = 5µA nominal

Calibration accuracy: dc ranges = ±15mV mA ranges = ±30µA

Temperature stability 100ppm/°C