•ModbusTM RTU protocol
•1200, 2400, 4800, 9600, 19200 baud rates
•32 maximum units can be connected (With additional
485 repeater hardware, up to 247 units may be connected)
Accuracy |
|
|
|
|
|
• Input ranges |
|
|
|
|
|
Type J: | 0 to | 750°C | or | 32 to | 1382°F |
Type K: | or | 2282°F | |||
Type T: | 350°C | or | 662°F | ||
Type N: | 0 to 1250°C | or | 32 to 2282°F | ||
Type E: | 900°C | or | 1470°F | ||
Type C(W5): | 0 to 2315°C | or | 32 to 4200°F | ||
Type D(W3): | 0 to 2315°C | or | 32 to 4200°F | ||
Type Pt 2: | 0 to 1393°C | or | 32 to | 2540°F | |
Type R: | 0 to 1450°C | or | 32 to 2642°F | ||
Type S: | 0 to 1450°C | or | 32 to 2642°F | ||
Type B: | 870 to 1700°C | or | 1598 to 3092°F | ||
DIN: | 800°C | or | 1472°F | ||
JIS: | 630°C | or | 1166°F | ||
Process: |
|
|
|
•Calibration accuracy ±0.1 percent of span ±1°C at standard conditions
Exceptions:
Type T; 0.12 percent of span for
•Accuracy span: 540°C/1000°F minimum
•Temperature stability: ±0.1 degree per degree change in ambient
RTD Inputs•Calibration accuracy ±0.1 percent of span ±1°C at standard conditions
•Accuracy span: 540°C/1000°F minimum
•Temperature stability: ±0.05 degree per degree change in ambient
Process Inputs•Voltage input ranges
Accuracy ±10mV ±1 LSD at standard conditions Temperature stability ±100ppm/°C maximum
•Milliamp input ranges
Accuracy ±20µA ±1 LSD at standard conditions Temperature stability ±100ppm/°C maximum
Agency Approvals• UL®916 file number E185611,
•Touch safe
•22 to 12 AWG
ModbusTM is a trademark of AEG Schneider Automation.
UL® and
•
•
•7.0VA maximum power consumption
•Data retention upon power failure via nonvolatile memory
Operating Environment•0 to 65°C, 32 to 149°F
•0 to 90% RH,
•Storage temperature:
•Width 52 mm (2.05 in.)
•Height 52 mm (2.05 in.)
•Length 107 mm (4.2 in.)
•Depth behind panel surface 98.4 mm (3.875 in.)
•Approximate controller weight 0.2 kg (0.4 lbs)
Allowable Operating RangesType J: | 1.0 | 0 to 815°C or | 32 to 1500°F |
0.10.0 to 815.0°C or 32.0 to 999.9°F
Type K: | 1.0 | to | 1370°C | or | to | 2500°F | ||
| 0.1 | to | 999.9°C | or | to | 999.9°F | ||
Type T: | 1.0 | to | 400°C | or | to | 750°F | ||
| 0.1 | to | 400.0°C | or | to | 750.0°F | ||
Type N: | 1.0 | 0 | to | 1300°C | or | 32 | to | 2372°F |
0.10.0 to 999.9°C or 32.0 to 999.9°F
Type E: | 1.0 | to | 800°C | or | to | 1470°F | ||
| 0.1 | to | 800.0°C | or | to | 999.9°F | ||
Type C: | 1.0 | 0 | to | 2315°C | or | 32 | to | 4200°F |
0.10.0 to 999.9°C or 32.0 to 999.9°F
Type D: | 1.0 | 0 to 2315°C or | 32 to 4200°F |
0.10.0 to 999.9°C or 32.0 to 999.9°F
Type Pt 2: 1.0 | 0 to 1395°C or | 32 to 2543°F |
0.10.0 to 999.9°C or 32.0 to 999.9°F
Type R: | 1.0 |
| 0 | to | 1760°C | or | 32 | to | 3200°F | |||
Type S: | 1.0 |
| 0 | to | 1760°C | or | 32 | to | 3200°F | |||
Type B: | 1.0 |
| 0 | to | 1816°C | or | 32 | to | 3300°F | |||
DIN | 1.0 |
| to | 800°C | or | to | 1472°F | |||||
| 0.1 | to | 800.0°C | or | to | 999.9°F | ||||||
JIS | 1.0 |
| to | 630°C | or | to | 1166°F | |||||
| 0.1 | to | 630.0°C | or | to | 999.9°F | ||||||
Process |
|
| to 9999 units |
|
|
|
| |||||
Functionality Matrix |
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| Event & |
|
|
|
|
|
|
| |
| Universal |
| Remote |
|
|
|
|
| 232/485 |
| ||
| Input |
|
| Set Point | Control | Alarm | Retransmit | Comm |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
Input 1 |
|
|
|
|
|
|
|
|
|
|
|
|
Input 2 |
|
|
|
|
|
|
|
|
|
|
|
|
Output 1 |
|
|
|
|
|
|
|
|
|
|
|
|
Output 2 |
|
|
|
|
|
|
|
|
|
|
|
|
Output 3 |
|
|
|
|
|
|
|
|
|
|
|
|
Output 4 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note: These specifications are subject to change without prior notice.