Communications

EIA/TIA-485 or EIA/TIA-232

Opto-isolated

ModbusTM RTU protocol

1200, 2400, 4800, 9600, 19200 baud rates

32 maximum units can be connected (With additional

485 repeater hardware, up to 247 units may be connected)

Accuracy

 

 

 

 

 

• Input ranges

 

 

 

 

 

Type J:

0 to

750°C

or

32 to

1382°F

Type K:

-200 to 1250°C

or

-328 to

2282°F

Type T:

-200 to

350°C

or

-328 to

662°F

Type N:

0 to 1250°C

or

32 to 2282°F

Type E:

-200 to

900°C

or

-328 to

1470°F

Type C(W5):

0 to 2315°C

or

32 to 4200°F

Type D(W3):

0 to 2315°C

or

32 to 4200°F

Type Pt 2:

0 to 1393°C

or

32 to

2540°F

Type R:

0 to 1450°C

or

32 to 2642°F

Type S:

0 to 1450°C

or

32 to 2642°F

Type B:

870 to 1700°C

or

1598 to 3092°F

DIN:

-200 to

800°C

or

-328 to

1472°F

JIS:

-200 to

630°C

or

-328 to

1166°F

Process:

-1999 to 9999 units

 

 

 

Thermocouple Inputs

Calibration accuracy ±0.1 percent of span ±1°C at standard conditions

Exceptions:

Type T; 0.12 percent of span for -200°C to -50°C, Types R and S; 0.15 percent of span for 0°C to 100°C Types B; 0.24 percent of span for 870°C to 1700°C

Accuracy span: 540°C/1000°F minimum

Temperature stability: ±0.1 degree per degree change in ambient

RTD Inputs

Calibration accuracy ±0.1 percent of span ±1°C at standard conditions

Accuracy span: 540°C/1000°F minimum

Temperature stability: ±0.05 degree per degree change in ambient

Process Inputs

Voltage input ranges

Accuracy ±10mV ±1 LSD at standard conditions Temperature stability ±100ppm/°C maximum

Milliamp input ranges

Accuracy ±20µA ±1 LSD at standard conditions Temperature stability ±100ppm/°C maximum

Agency Approvals

• UL®916 file number E185611, C-UL®, CE, NEMA 4X

Terminals

Touch safe

22 to 12 AWG

ModbusTM is a trademark of AEG Schneider Automation.

UL® and C-UL®are registered trademarks of the Underwriter’s Laboratories, Inc.

Power

100-240Vı(ac/dc) +10 percent, -15 percent; 50/60Hz, ±5 percent

24-28Vı(ac/dc) +10 percent, -15 percent; 50/60Hz, ±5 percent

7.0VA maximum power consumption

Data retention upon power failure via nonvolatile memory

Operating Environment

0 to 65°C, 32 to 149°F

0 to 90% RH, non-condensing

Storage temperature: -40 to 85°C, -40 to 185°F

Dimensions

Width 52 mm (2.05 in.)

Height 52 mm (2.05 in.)

Length 107 mm (4.2 in.)

Depth behind panel surface 98.4 mm (3.875 in.)

Approximate controller weight 0.2 kg (0.4 lbs)

Allowable Operating Ranges

Type J:

1.0

0 to 815°C or

32 to 1500°F

0.10.0 to 815.0°C or 32.0 to 999.9°F

Type K:

1.0

-270

to

1370°C

or

-454

to

2500°F

 

0.1

-199.9

to

999.9°C

or -199.9

to

999.9°F

Type T:

1.0

-270

to

400°C

or

-454

to

750°F

 

0.1

-199.9

to

400.0°C

or -199.9

to

750.0°F

Type N:

1.0

0

to

1300°C

or

32

to

2372°F

0.10.0 to 999.9°C or 32.0 to 999.9°F

Type E:

1.0

-270

to

800°C

or

-454

to

1470°F

 

0.1

-199.9

to

800.0°C

or -199.9

to

999.9°F

Type C:

1.0

0

to

2315°C

or

32

to

4200°F

0.10.0 to 999.9°C or 32.0 to 999.9°F

Type D:

1.0

0 to 2315°C or

32 to 4200°F

0.10.0 to 999.9°C or 32.0 to 999.9°F

Type Pt 2: 1.0

0 to 1395°C or

32 to 2543°F

0.10.0 to 999.9°C or 32.0 to 999.9°F

Type R:

1.0

 

0

to

1760°C

or

32

to

3200°F

Type S:

1.0

 

0

to

1760°C

or

32

to

3200°F

Type B:

1.0

 

0

to

1816°C

or

32

to

3300°F

DIN

1.0

 

-200

to

800°C

or

-328

to

1472°F

 

0.1

-199.9

to

800.0°C

or -199.9

to

999.9°F

JIS

1.0

 

-200

to

630°C

or

-328

to

1166°F

 

0.1

-199.9

to

630.0°C

or -199.9

to

999.9°F

Process

 

 

-1999

to 9999 units

 

 

 

 

Functionality Matrix

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Event &

 

 

 

 

 

 

 

 

Universal

 

Remote

 

 

 

 

 

232/485

 

 

Input

 

 

Set Point

Control

Alarm

Retransmit

Comm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input 1

 

 

 

 

 

 

 

 

 

 

 

 

Input 2

 

 

 

 

 

 

 

 

 

 

 

 

Output 1

 

 

 

 

 

 

 

 

 

 

 

 

Output 2

 

 

 

 

 

 

 

 

 

 

 

 

Output 3

 

 

 

 

 

 

 

 

 

 

 

 

Output 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: These specifications are subject to change without prior notice.