GAS INSTRUCTIONS

LOCATING YOUR BUILT-IN SIDE BURNER

When determining a suitable location for your Built-In Side Burner installation, give attention to concerns such as exposure to wind, proximity to traffic paths, and keeping any gas supply lines as short as possible. Never locate the Summit® Built-In Side Burner in a garage, breezeway, shed, under an unprotected overhang, or other enclosed area. Locate the Side Burner and structure so there is enough room to safely evacuate the area in case of a fire.

CLEARANCE FROM COMBUSTIBLE SURFACES OR STRUCTURES

WARNING: Clearance from the outside walls of the sides and back of the Built-In Side Burner must be a minimum of 24 inches (61 cm) any surface. Refer to “Typical Gas Supply Installation” before starting installation.

WARNING: The structure, “island” counter tops and adjacent work areas for the Built-In Side Burner installation must be built from noncombustible materials only.

A B

1

B

C

2

B A

NOTE: If you have questions on what materials are considered noncombustible, contact you local building supplier or fire department.

 

SIDE BURNER LOCATION

 

 

A

Any Surface

B

24” (61 cm) From Any Surface

C

Side Burner

1

24” ( 61 cm) Minimum Lid Clearance

2Note: For a countertop treatment: Recommended 3/4” (19 mm) overhang. Notch front edge for frame to fully slide in.

BUILT-IN STRUCTURE CUTOUT DIMENSIONS

All dimensions are to finished surfaces.

WARNING: All counter top finished surfaces must be constructed of a noncombustible material.

SIDE BURNER

 

Cut out Dimensions

Tolerances

 

 

 

 

 

A

10

1/2” (26.7 cm)

+ 1/4”

- 1/4” (6.35mm)

B

3

3/4” (9.5 cm)

+ 1/4”

- 1/4” (6.35mm)

C

16 1/4” (41.3 cm)

+ 1/4”

- 1/4” (6.35mm)

WWW.WEBER.COM®

Page 4
Image 4