Weber 42377 manual Typical Natural Gas Supply Installation, General Specifications For Piping

Models: 42377 Summit Built-In NG Side Burner

1 12
Download 12 pages 30.93 Kb
Page 6
Image 6
TYPICAL NATURAL GAS SUPPLY INSTALLATION

6

GAS INSTRUCTIONS

 

 

TYPICAL NATURAL GAS SUPPLY INSTALLATION

We recommend that this installation be done by a LICENSED professional.

GENERAL SPECIFICATIONS FOR PIPING

Note - Contact your local municipality for building codes regulating outdoor gas grill installations. In absence of Local Codes, you must conform to the latest edition of National Fuel Gas Code ANSI Z223.1/NFPA54.

This grill is designed to operate at 4.5 inches of water column pressure.

A manual shut-off valve must be installed outdoors, and be accessible, not in the “built-in” structure. An additional manual shut-off valve indoors should be installed in the branch fuel line in an accessible location near the supply line.

CAUTION: If young children are in the area, a locking valve should be considered.

Pipe compound should be used which is resistant to the action of liquid propane gas when gas connections are made.

The gas connections must be fi rmly attached to a rigid, permanent construction.

Note: The information provided in this manual is general for typical installations. We cannot cover all possible installation ideas. We recommend, prior to installation, that you contact your municipality for local building codes and your local fire department for installation verification.

If you have any questions, contact Customer Service at 1-800-446-1071.

GAS LINE PIPING

Refer to the piping chart at the bottom of previous page.

The corrugated gas line from the manifold is 58 inches long. Do not extend the gas line.

We have provided the means to make an SAE 45° fl are connection. Do not use pipe sealant on this connection.

If the length of line required does not exceed 50 feet, use a 5/8” O.D. tube. One size larger should be used for lengths greater than 50 feet. Refer to piping chart.

Gas piping may be copper tubing, type K or L; polyethylene plastic tube, with a minimum wall thickness of .062 inch; or standard weight (schedule 40) steel or wrought iron pipe.

Copper tubing must be tin-lined if the gas contains more than 0.3 grams of hydrogen sulfi de per 100 cubic feet of gas.

Plastic tubing is suitable only for outdoor, underground use.

Gas piping in contact with earth, or any other material which may corrode the piping, must be protected against corrosion in an approved manner.

Underground piping must have a minimum of 18” cover.

Table

Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of 0.5 psi or Less and a Pressure Drop of 0.3 Inch

10-1

 

 

 

 

Water Column. (Based on a 0.60 Specific Gravity Gas)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

Internal

 

 

 

 

 

 

Length of Pipe (Feet)

 

 

 

 

 

 

Iron Pipe

Diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

(Inches)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

(Inches)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4

.364

32

22

18

15

14

12

11

11

10

9

8

8

7

6

3/8

.493

72

49

40

34

30

27

25

23

22

21

18

17

15

14

1/2

.622

132

92

73

63

56

50

46

43

40

38

34

31

28

26

3/4

.824

278

190

152

130

115

105

96

90

84

79

72

64

59

55

1

1.049

520

350

285

245

215

195

180

170

160

150

130

120

110

100

1 1/4

1.380

1050

730

590

500

440

400

370

350

320

305

275

250

225

210

1 1/2

1.160

1600

1100

890

760

670

610

560

530

490

460

410

380

350

320

2

2.067

3050

2100

1650

1450

1270

1150

1050

990

930

870

780

710

650

610

2 1/2

2.469

4800

3300

2700

2300

2000

1850

1700

1600

1500

1400

1250

1130

1050

980

3

3.068

8500

5900

4700

4100

3600

3250

3000

2800

2600

2500

2200

2000

1850

1700

4

4.026

17500

12000

9700

8300

7400

6800

6200

5800

5400

5100

4500

4100

3800

3500

 

 

 

 

 

©1997 National Fire Protection Association, Inc., and International Approval Services - U.S., Inc. All Rights Reserved.

 

 