APPLICATION FIELD WIRING

GB

APPLICATION FIELD WIRING

WIRING DIAGRAM SHOWN BELOW FOR STANDARD RIELLO 530 SE/C PRIMARY CONTROL BOX.

INSTALLATION NOTE: ELECTRONIC AIR SHUTTER REQUIRES A CONSTANT 120V POWER SUPPLY TO THE AUX TERMINAL, FAILURE TO PROVIDE THIS WILL RESULT IN NO BURNER OPERATION OR AIR SHUT- TER WILL NOT CLOSE.

AIR SHUTTER

AIR SHUTTER

MOTOR

MOTOR

24V SWITCHING RELAY

PLEASE NOTE: OPERATING LIMIT AND SAFETY LIMIT ARE TWO SEPARATE LIMITS. Key to lay-out:

1- Main disconnect fuse

2- Manual service switch

3- Safety limit device

4- Operating limit device

5- Earth ground connection burner chassis

6- Burner control remote lock out alarm device - wired & supplied by others AUX - Auxiliary bub base add-on connector (air shutter)

T - T - 24V thermostat connections - low voltage operated system

MIN. WIRE SIZE:

 

INSULATED 18 AWG SOLID OR 16 STRD.

RATED 105° C

PROPER EARTH GROUNDING MEANS REQUIRED

ALL WIRING SHOWN PROVIDED BY OTHER.

WARNING: DO NOT activate burner until proper oil line connections have been made, or failure of the pump shaft seal may occur.

WARNING: DO NOT activate burner until all safety and operating controls have been wired in series with the burner, as required by local code authorities and/or as specified by the appliance manufacturer.