Weil-McLain Burner Specifications

Weil-McLain Burner Specifications

NOTICE

The remainder of this manual contains Information to be used ONLY by a

qualified Service Technician.

NX Burner Specifications for Weil-McLain Ultra Oil Boilers

Verify that burner specification number (on burner carton) and configuration agrees with information below.

Table 1. Burner Configurations

The table below provides burner specifications and starting air settings for NX burners applied to Weil-McLain Model UO boilers. Follow all instructions in this burner manual, the boiler manual and the fuel pump literature to install, setup and service the burner.

Boiler

Burner

Firing

Air Tube

Inser-

Primary

Alternate

Fuel

Head/

Model

Spec

Rate

Combina-

tion

Nozzle

Nozzle

Pump

Air

 

 

(GPH)

tion

 

 

 

Pres-

Adjust-

 

 

 

 

 

 

 

sure

ment

 

 

 

 

 

 

 

(psig)

Plate

 

 

 

 

 

 

 

 

Setting

UO-3 CV

WL5703

0.80

NX70LC

1-3/4”

0.65 X 60oA

0.65 X 70oB

150

1.75

 

(See Note1)

 

 

 

Delavan

Hago

 

 

 

 

 

 

 

 

 

 

 

UO-3 CV

WL5703

1.00

NX70LC

1-3/4”

0.75 X 60oB

0.75 X 60oB

175

2.50

 

 

 

 

 

Hago

Delavan

 

 

UO-4 CV

WL5704

1.20

NX90LB

3-1/2”

1.00 X 70oB

1.00 X 70oB

140

4.00

 

 

 

 

 

Hago

Delavan

 

 

UO-5 CV

WL5705

1.40

NX90LD

3-1/2”

1.10 X 70oB

1.10 X 70oB

160

1.50

 

 

 

 

 

Hago

Delavan

 

 

UO-3 DV

WL5803

0.80

NX70LC

1-3/4”

0.65 X 60oA

0.65 X 70oB

150

1.75

 

(See Note1)

 

 

 

Delavan

Hago

 

 

UO-3 DV

WL5803

1.00

NX70LC

1-3/4”

0.75 X 60oB

0.75 X 60oB

175

2.50

 

 

 

 

 

Hago

Delavan

 

 

UO-4 DV

WL5804

1.20

NX90LB

3-1/2”

1.00 X 70oB

1.00 X 70oB

140

4.00

 

 

 

 

 

Hago

Delavan

 

 

UO-5 DV

WL5805

1.40

NX90LD

3-1/2”

1.10 X 70oB

1.10 X 70oB

160

1.50

 

 

 

 

 

Hago

Delavan

 

 

1)Shipped as 1.0 GPH Burner Configuration. The 0.80 GPH input uses same burner as 1.0 GPH input. Replace nozzle, adjust pump pressure and Head/Air setting as shown above and install 14”x16” blanket on combustion chamber floor. (See Maintenance Section for Nozzle Replacement details.)