Burner specifications and settings
Table 1 | Burner data — Natural gas — Modulating |
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Boiler |
| Burner | Pressure | Manifold | Gas Pressure Required at | Gas Pilot | Combustion |
| Combustion |
|
| Servo Motor Cam |
|
| |||
Model |
| Model | Drop Thru | Pressure | Gas Control Inlet | Pressure | Head |
| Air Settings |
|
| Position Settings |
|
| |||
Number |
| Number | Gas Train . |
|
|
|
| Setting |
|
|
|
|
|
|
|
|
|
| Min | Max |
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
| Inches W.C. | Inches W.C. | Inches W.C | Inches W.C | Inches W.C. |
|
|
|
|
|
|
|
|
|
|
488R |
| RS28/M | 0.75 | 3.30 | 4.05 | 14 | 5.00 | 3 | 27 |
| 52 | 0 | 22 | 90 | — | — | — |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
488 |
| RS28/M | 0.75 | 3.60 | 4.30 | 14 | 5.00 | 4 | 27 |
| 52 | 0 | 22 | 90 | — | — | — |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
588 |
| RS38/M | 1.30 | 3.70 | 5.00 | 14 | 5.00 | 2 | 17 |
| 70 | 0 | 25 | 90 | — | — | — |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
688 |
| RS50/M | 1.83 | 2.90 | 4.73 | 14 | 2.70 | 3 | 16 |
| 65 | 0 | 18 | 90 | — | — | — |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
788 |
| RS50/M | 2.40 | 3.50 | 5.85 | 14 | 2.50 | 4 | 28 |
| 85 | 0 | 20 | 90 | — | — | — |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
888 |
| RS70/M | 2.98 | 3.70 | 6.63 | 14 | 8.25 | 3 | 2.5 |
| 7.0 | — | — | — | 130 | 0 | 35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
988R |
| RS70/M | 3.16 | 3.87 | 7.03 | 14 | 8.25 | 4 | 2.5 |
| 7.5 | — | — | — | 130 | 0 | 35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
988 |
| RS70/M | 3.16 | 4.10 | 7.28 | 14 | 8.25 | 5 | 2.5 |
| 7.5 | — | — | — | 130 | 0 | 35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1088R |
| RS70/M | 3.00 | 4.65 | 7.65 | 14 | 6.50 | 8 | 3.0 |
| 8.5 | — | — | — | 130 | 0 | 40 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1088 |
| RS70/M | 3.00 | 4.90 | 7.90 | 14 | 6.50 | 9 | 3.0 |
| 8.5 | — | — | — | 130 | 0 | 40 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1188 |
| RS100/M | 3.80 | 3.10 | 6.90 | 14 | 6.50 | 4 | 2.5 |
| 6.0 | — | — | — | 130 | 0 | 35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1288 |
| RS100/M | 3.82 | 3.63 | 7.45 | 14 | 7.50 | 4 | 3.0 |
| 6.5 | — | — | — | 130 | 0 | 35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1388 |
| RS100/M | 2.41 | 4.50 | 6.91 | 14 | 7.60 | 3 | 2.5 |
| 9.0 | — | — | — | 130 | 0 | 30 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1488 |
| RS130/M | 3.76 | 3.30 | 7.01 | 14 | 7.80 | 5 | 2.0 |
| 7.0 | — | — | — | 130 | 0 | 50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1588 |
| RS130/M | 4.09 | 3.50 | 7.59 | 14 | 7.20 | 7 | 2.5 |
| 7.0 | — | — | — | 130 | 0 | 50 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1688R |
| RS130/M | 3.19 | 3.45 | 6.64 | 14 | 7.20 | 8 | 2.5 |
| 8.5 | — | — | — | 130 | 0 | 30 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1688 |
| RS130/M | 3.19 | 3.70 | 6.89 | 14 | 7.20 | 9 | 2.5 |
| 8.5 | — | — | — | 130 | 0 | 30 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1788 |
| RS130/M | 3.70 | 4.80 | 8.50 | 14 | 7.20 | 9 | 2.5 |
| 9.0 | — | — | — | 130 | 0 | 55 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1888 |
| RS190/M | 3.71 | 3.50 | 7.21 | 14 | 5.00 | 0 | 0.5 |
| 3.8 | — | — | — | 130 | 0 | 45 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes for Table 1, Table 2 and Table 3
1.Burner capacities listed for elevations up to 2,000 feet. For higher eleva- tions, consult local
2.Gas ratings based on natural gas with heating value of 1,000 Btu per cubic foot and specific gravity of 0.60. Gas burners for other gases are available. Consult local
3.
4.Minimum gas pressures listed are subject to variations due to job condi- tions. Gas burners for other gas pressures are available. Consult local
5.All settings and pressures shown are for initial
6.Gas train sizes for models 488R to 1288 are based on a supply pressure to the regulator of 7 inches W.C. Gas train sizes for models 1388 to 1888 are based on a supply pressure to the regulator of 12 inches W.C. Optional trains are available for other pressures upon request.
7.Gas Control Systems:
•OO: On - Off operation.
•LHL:
•MOD: On - Off operation with proven low fire start and full modulating firing conditions. Proportional motor drives fuel metering valve and combustion air damper according to firing conditions; open damper
8.120/60/1 control circuit is used for all burners. Control circuit trans- former is available as an option.
9.Airflow safety switch is standard for all gas and combination gas/light oil units.
10.Burners will be completely assembled and wired (except gas train) and factory
11.Special controls can be provided to meet other code requirements not listed. Consult your local
12.Direct spark ignition is standard for light oil units. Direct spark ignition is available as an option for combination gas/light oil units. Consult your local
13.All 3 phase models require a separate 120/60/1 control voltage supply.
14.Combustion Controls:
•Siemens LFL 1.335 flame safeguard control monitors the oil or gas burner flame with visual diagnostic window, provides
15.All units require a single SPDT controller for LHL firing rate opera- tion.
16.Modulating units 488R to 788 require a 120v bumping type signal or PID control for modulation.
17.Modulating units 888 to 1888 require a 4 – 20mA, 0 – 10vdc or 135 ohm signal for modulation.
18.Motor relay or contractor will be furnished on all units.