Burner Specification & Data sheet — Riello Gas Burners
Burner specifications and settings (continued)
Table 2 | Burner data — Natural gas — General |
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
Boiler | Burner | Positive | Standard Burner Model | Standard | Standard | Burner Motor H.P. |
|
| Standard | ||||
Model | Input | Pressure In | Designation | Combustion | Control System | 3400 RPM |
|
| Motor Voltage | ||||
Number |
| Firebox |
|
| Control |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Inches W.C. | On - Off | LHL/MOD | Note 14 | On - Off | LHL/MOD | On - Off | LHL/MOD | On - Off |
| LHL/MOD | |
488R | 996 | .89 | RS28/1 | RS28/M | LFL 1.335** | 00 | LHL/MOD | 1/2 |
| 1/2 | 120/60/1 |
| 120/60/1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
488 | 1010 | 1.00 | RS28/1 | RS28/M | LFL 1.335** | 00 | LHL/MOD | 1/2 |
| 1/2 | 120/60/1 |
| 120/60/1 |
|
|
|
|
|
|
|
|
|
|
|
|
| |
588 | 1357 | .89 | RS38/1 | RS38/M | LFL 1.335** | 00 | LHL/MOD | 1/2 | 1/2 OR 3/4 | 120/60/1 |
| 120/60/1 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
688 | 1703 | .72 | — | RS50/M | LFL 1.335** | — | LHL/MOD | — |
| 3/4 | — |
| 120/60/1 or 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
788 | 2049 | .65 | — | RS50/M | LFL 1.335** | — | LHL/MOD | — |
| 3/4 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
888 | 2396 | .85 | — | RS70/M | LFL 1.335** | — | LHL/MOD | — | 1 | 1/2 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
988R | 2482 | .80 | — | RS70/M | LFL 1.335** | — | LHL/MOD | — | 1 | 1/2 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
988 | 2713 | .80 | — | RS70/M | LFL 1.335** | — | LHL/MOD | — | 1 | 1/2 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1088R | 2887 | .82 | — | RS70/M | LFL 1.335** | — | LHL/MOD | — | 1 | 1/2 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1088 | 3103 | .82 | — | RS100/M | LFL 1.335** | — | LHL/MOD | — | 2 | 1/2 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1188 | 3392 | .82 | — | RS100/M | LFL 1.335** | — | LHL/MOD | — | 2 | 1/2 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
| |
1288 | 3753 | .81 | — | RS100/M | LFL 1.335** | — | LHL/MOD | — | 2 1/2 | — |
| 3 phase* | |
|
|
|
|
|
|
|
|
|
|
|
|
| |
1388 | 4113 | .89 | — | RS100/M | LFL 1.335** | — | LHL/MOD | — | 2 1/2 | — |
| 3 phase* | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1488 | 4474 | .86 | — | RS130/M | LFL 1.335** | — | LHL/MOD | — |
| 3 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1588 | 4763 | .86 | — | RS130/M | LFL 1.335** | — | LHL/MOD | — |
| 3 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1688R | 4979 | .863 | — | RS130/M | LFL 1.335** | — | LHL/MOD | — |
| 3 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1688 | 5124 | .83 | — | RS130/M | LFL 1.335** | — | LHL/MOD | — |
| 3 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1788 | 5485 | .82 | — | RS130/M | LFL 1.335** | — | LHL/MOD | — |
| 3 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1888 | 5845 | .85 | — | RS190/M | LFL 1.335** | — | LHL/MOD | — |
| 3 | — |
| 3 phase* |
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| *208/60/3, 240/60/3, 480/60/3, 575/60/3, burner motor voltage must be specified | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Table 3 | Gas control components and sizes |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |
Boiler |
| Manual | Low Gas | Gas | Operating | Operating Gas | Safety | Manual | High Gas | |
Model |
| Hand Valve | Pressure Switch | Pressure Regulator | Gas Valve | Valve (with Proof Of | Gas Valve | Checking Gas Valve | Pressure Switch | |
Number |
|
|
|
|
| Closure) |
|
|
| |
| Inches |
| Inches | Inches | Inches | Inches |
| |||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| |
488R – 688 |
| 1 1/2 | Standard | 1 1/2 | 1 1/2 | Optional | 1 1/2 | 1 1/2 | Standard | |
|
|
|
|
|
|
|
|
|
| |
788 – 1188 |
| 2 | Standard | 2 | 2 | Optional | 2 | 2 | Standard | |
|
|
|
|
|
|
|
|
|
|
|
1288 | – 1688R |
| 2 1/2 | Standard | 2 1/2 | 2 1/2 | Optional | 2 1/2 | 2 1/2 | Standard |
|
|
|
|
|
|
|
|
|
|
|
1688 | – 1888 |
| 3 | Standard | 3 | 3 | Optional | 3 | 3 | Standard |
|
|
|
|
|
|
|
|
|
|
|
Part No. | 3 |