Installation

GOLD GV Water boiler — Series 3

Installation

Pre-installation planning

1.Follow national, state, local or provincial codes or regulations when venting GV boiler.

2.Choose vent method from those shown on page 5.

3.Select vent run components from Table 2. Table 3 states maximum vent run lengths and number of elbows. Do not exceed data in Table 3. Longer vent runs will slightly reduce boiler output. See Figure 2.

4.If installing with direct vent method, use same maximum run length and number of elbows from

step 2. Vent and combustion air connector piping configurations must match. Use suitable 3" material for combustion air connector piping, such as:

Dryer vent

Galvanized steel

PVC (3" I.D.)

5.Refer to vent termination WARNING, item 19 on page 3.

Table 2

 

Description

Flex-L International, Inc.

 

 

 

Part Number (Note 1)

Parts list

GV starter tee

--

 

 

 

 

GV termination coupling

SRAWGVT

 

 

45o elbow

SRE4503

 

 

90o elbow

SRE9003

 

 

6" pipe

SR06P03

 

 

1' pipe

SR12P03

 

 

2' pipe

SR24P03

 

 

3' pipe

SR36P03

 

 

5' pipe

SR60P03

 

 

Joiner band

SRJB-14

 

 

Weil-McLain Vent/Air Intake Termination Kit

382-200-430 (Note 2)

 

 

Weil-McLain Through-Roof or Through-Unused-Chimney Termination Kit

382-200-435 (Note 2)

 

 

Notes

 

 

 

1. Flex-L International, Inc. part number. Parts available through Flex-L International, Inc.

 

 

2. Weil-McLain part number. Parts available through Weil-McLain distributor.

 

 

 

 

 

Table 3

Vent and combustion air connector piping lengths and number of elbows

Maximum vent

 

Total number of elbows

 

length (feet)

 

 

 

 

 

 

 

 

0

2

3

4

5

6

7

8

 

 

 

 

 

 

 

 

 

 

GV-3 through GV-5

100

80

70

60

50

40

30

20

 

 

 

 

 

 

 

 

 

GV-6

80

60

50

40

30

20

10

--

 

 

 

 

 

 

 

 

 

Figure 2 Boiler output

 

100

 

 

 

 

 

 

99

 

 

 

 

GV-3

 

 

 

 

 

 

Output

 

 

 

 

 

GV-4

98

 

 

 

 

 

 

 

 

 

 

GV-5

97

 

 

 

 

GV-6

%

 

 

 

 

 

 

 

 

 

 

 

96

 

 

 

 

 

 

95

 

 

 

80

 

 

0

20

40

60

100

26800

Total equivalent length (feet) of vent
(from boiler to vent termination)

 

4

Part Number 550-110-268/0699

Page 4
Image 4