Weil-McLain WMBC-1A manual Gas piping, III Wiring

Models: WMBC-1A

1 11
Download 11 pages 40.79 Kb
Page 5
Image 5
Gas piping

Flame Guardian WMBC-1A Electronic Pilot System – IRI

II

Table 2

Natural gas supply pipe sizing

Gas piping

1.Size gas piping considering:

a.Diameter and length of gas supply piping.

b.Number of fittings.

c.Maximum gas consumption (including any possible future expansion).

d.Allowable pressure drop from gas meter outlet to boiler. For pressure drops, see ANSI-Z223.1 – latest edition.

2.Size natural gas piping from table below. Size piping to provide proper inlet pressure to gas valve when operating at rated input.

a.Inlet gas pressure to manual main shutoff gas valve minimum 7” W.C. standard (5½” on special order) – maximum 13” W.C.

b.If pressure to gas valve exceeds 13”W.C., install positive dead-end lockup gas pressure regulator up stream of hand valve.

c.To obtain approximate cubic feet per hour, divide input (BTU/HR) by 1000.

3.Remove gas supply knockout disc from jacket panel.

4.Follow good piping practices.

5.Pipe joint compound (pipe dope) must be resistant to corrosive action of liquefied petroleum gases. Apply sparingly only to male threads of pipe joints.

6.Install drip leg at inlet of gas connection to boiler. Where local utility requires, extend drip leg to floor.

7.Install ground joint union when required for servicing.

8.Support piping by hangers, not by boiler or its accessories.

9.Purge all air from supply piping.

10.Check all connections for leaks.

Do not check for gas leaks with an open flame – BUBBLE TEST. Failure to use bubble test or test for leaks can cause severe personal injury, death or substantial property damage.

a.Close manual main shutoff valve during any pressure testing at less than 14.0 inches water column.

b.Disconnect boiler and gas controls from gas supply piping during any pressure test greater than 14.0 inches water column.

11.Set gas pressure switches as follows or to local inspector’s requirements:

a. Low – 3.0” W.C.

 

b. High – 14.0” W.C

 

 

 

 

 

 

 

 

PIPE

PIPE LENGTH, FEET (NATURAL GAS CAPACITIES, LISTED IN MBH)

 

 

SIZE

(Specific Gravity 0.60 @ Pressure Loss of 0.30" w.c.)

 

 

 

 

10’

20’

30’

40’

50’

75’

100’

150’

1¼"

1,050

730

590

500

440

360

305

250

1½"

1,600

1,100

890

760

670

545

460

380

2"

3,050

2,100

1,650

1,450

1,270

1,020

870

710

2½"

4,800

3,300

2,700

2,300

2,000

1,650

1,400

1,130

3"

8,500

5,900

4,700

4,100

3,600

2,900

2,500

2,000

4"

17,500

12,000

9,700

8,300

7,400

6,000

5,100

4,100

* Include measured length of gas supply piping and allowance in feet for number and size of fittings.

III Wiring

For your safety, turn off electrical power supply before making any electrical connections to avoid possible electrical shock hazard.

1.All wiring must be installed in accordance with the requirements of the National Electrical Code and any additional national, state or local code requirements having jurisdiction. All wiring must be N.E.C. Class 1.

2.The boiler must be electrically grounded in accordance with the National Electrical Code, ANSI/NFPA No. 70- latest edition. Use 105 °C. thermoplastic wire, or equivalent, if any of the original wire must be replaced (except for pilot spark, sense and ground wires).

3.Supply wiring to the boiler must be No. 14 gauge or heavier. Install in conduit.

4.A separate electrical circuit with a fused disconnect switch (15 amp. recommended) should be used for the boiler.

Part Number 550-141-807/0298

5

Page 5
Image 5
Weil-McLain WMBC-1A manual Gas piping, III Wiring