Whirlpool W10123251, 315422-000, SG1J5040T3NOV 7K, SG1J4040T3NOV 7K Closed System/Thermal Expansion

Models: W10123251 SG1J5040T3NOV 7K SG1J4040T3NOV 7K 315422-000

1 32
Download 32 pages 40.1 Kb
Page 13
Image 13
Closed System/Thermal Expansion

Please note the following:

The system should be installed only with piping that is suitable for potable (drinkable) water such as copper, CPVC, or polybutylene. This water heater must not be installed using iron piping or PVC water piping.

Use only pumps, valves, or fittings that are compatible with potable water.

Use only full flow ball or gate valves. The use of valves that may cause excessive restriction to water flow is not recommended.

Use only 95/5 tin-antimony or other equivalent solder. Any lead based solder must not be used.

Piping that has been treated with chromates, boiler seal, or other chemicals must not be used.

Chemicals that may contaminate the potable water supply must not be added to the piping system.

Closed System/Thermal Expansion

Manual backgroundWARNING

Explosion Hazard

If the temperature and pressure relief valve is dripping or leaking, have a qualified person replace it.

Examples of a qualified person include: licensed plumbers, authorized gas company personnel, and authorized service personnel.

Do not plug valve. Do not remove valve.

Failure to follow these instructions can result in death, or explosion.

Periodic discharge of the temperature and pressure relief valve may be due to thermal expansion in a closed water supply system. The water utility supply meter may contain a check valve, backflow preventer or water pressure reducing valve. This will create a closed water system. During

the heating cycle of the water heater, the water expands causing pressure inside the water heater to increase. This may cause the temperature and pressure relief valve to discharge small quantities of hot water. To prevent this, it is recommended that a diaphragm-type expansion tank (suitable for potable water) be installed on the cold water supply line. The expansion tank must have a minimum capacity of 1.5 U.S. gallons for every 50 gallons of stored water. Contact the local water supplier or plumbing inspector for information on other methods to control this situation.

IMPORTANT: Do not plug or remove the temperature and pressure relief valve.

13

Page 13
Image 13
Whirlpool W10123251, 315422-000, SG1J5040T3NOV 7K, SG1J4040T3NOV 7K installation instructions Closed System/Thermal Expansion

FAQ

What type of piping should be used for Whirlpool water heaters?

Only piping suitable for potable drinkable water such as copper, CPVC, or polybutylene should be used. Iron piping or PVC water piping is not recommended.

Why is it important to use only full flow ball or gate valves?

Using valves that may cause excessive restriction to water flow is not recommended, hence only full flow ball or gate valves should be used to ensure proper water flow.

How can I prevent the temperature and pressure relief valve from discharging hot water?

To prevent the discharge of hot water, it is recommended to install a diaphragm-type expansion tank suitable for potable water on the cold water supply line, or consult the local water supplier or plumbing inspector for other methods to control this situation.