Whirlpool SG1J5040T3NOV 7K Problem, Possible Causes, Corrective Action, Pilot Will Not Remain Lit

Models: W10123251 SG1J5040T3NOV 7K SG1J4040T3NOV 7K 315422-000

1 32
Download 32 pages 40.1 Kb
Page 26
Image 26

PROBLEM

 

POSSIBLE CAUSE(S)

 

CORRECTIVE ACTION

PILOT WILL NOT REMAIN LIT

1.

Air in gas line

1.

Bleed the air from the gas line

 

2.

Dirt in gas lines

2.

Notify utility-install dirt trap in gas line

 

3.

Pilot line or orifice clogged

3.

Clean, locate source and correct

 

4.

Thermocouple connection loose

4.

Finger tighten; then 1/2 turn with wrench

 

5.

Non-functioning thermocouple

5.

Replace thermocouple

 

6.

Cold drafts

6.

Locate source and correct

 

7.

Flammable vapors incident, Flame

7.

Eliminate flammable vapor source(s)

 

8.

LockTM function utilized

8.

Call 1-877-817-6750

 

Low gas pressure

Check with gas utility company

 

9.

Air for combustion obstructed

9.

See maintenance section for inspection and

 

10.

Pilot dirty

10.

cleaning of flame-trap & burner

 

Clean pilot

HIGH OPERATION COSTS

1.

Thermostat set too high

1.

Set temperature dial to lower setting

 

2.

Sediment or lime in tank

2.

Drain/flush-provide water treatment if needed

 

3.

Water heater too small for job

3.

Install adequate heater

 

4.

Wrong piping connections

4.

Correct piping-dip tube must be in cold inlet

 

5.

Leaking faucets

5.

Repair faucets

 

6.

Gas leaks

6.

Check with utility-repair at once

 

7.

Wasted hot water

7.

Advise customer

 

8.

Long runs of exposed piping

8.

Insulate piping

 

9.

Hot water piping in exposed wall

9.

Insulate piping

INSUFFICIENT HOT WATER

1.

Thermostat set too low

1.

Turn temperature dial to desired setting

 

2.

Sediment or lime in tank

2.

Drain/flush-provide water treatment if needed

 

3.

Water heater too small

3.

Install adequate heater

 

4.

Wrong piping connections

4.

Correct piping-dip tube must be in cold inlet

 

5.

Leaking faucets

5

Repair faucets

 

6.

Wasted hot water

6.

Advise customer

 

7.

Long runs of exposed piping

7.

Insulate piping

 

8.

Hot water piping in outside wall

8.

Insulate piping

 

9.

Low gas pressure

9.

Check with gas utility company

SLOW HOT WATER

1.

Insufficient air

1.

Provide ventilation to water heater. Check flue

RECOVERY

2.

Flue clogged

2.

way, flue baffle, and burner

 

Clean flue, locate source and correct

 

3.

Low gas pressure

3.

Check with gas utility company

 

4.

Improper calibration

4.

Replace thermostat

 

5.

Thermostat set too low

5.

Turn temperature dial to desired setting

 

6.

Water heater too small

6.

Install adequate heater

 

7.

Wrong piping connections

7.

Correct piping-dip tube must be in cold inlet

 

8.

Wasted hot water

8.

Advise customer

DRIP FROM RELIEF VALVE

1.

Excessive water pressure

1.

Use a pressure reducing valve and relief

 

2.

Heater stacking

2.

valve

 

Lower the thermostat setting

 

3.

Closed water system

3.

See “Closed System/Thermal Expansion”

THERMOSTAT FAILS TO

1.

Non-functioning thermostat

1.

Replace thermostat

SHUT OFF

2.

Improper calibration

2.

Replace thermostat

COMBUSTION ODORS

1.

Insufficient air

1.

Provide ventilation to water heater. Check flue

 

2.

Flue clogged

2.

way, flue baffle, and burner

 

Clean, locate source and correct

 

3.

Heater installed in a confined area

3.

Provide fresh air ventilation

SMOKING AND CARBON

1.

Flammable vapor incident

1.

Call 1-877-817-6750

FORMATION (SOOTING)

 

 

 

 

CONDENSATION

1.

Temperature setting too low

1.

Increase the temperature setting

 

 

 

 

 

BURNER FLAME FLOATS

1.

Orifice too large

1.

Replace with correct orifice

AND LIFTS OFF PORTS

2.

High gas pressure

2.

Check with gas utility company

 

3.

Flue clogged

3.

Clean flue and burner-locate source and

 

4.

Cold drafts

4.

correct

 

Locate source and correct

 

5.

Dirty burner screen

5.

Clean burner screen. See “Natural Gas Burner

 

 

 

 

(Ultra Low Nox)” section of this manual.

FLAME BURNS AT ORIFICE

1.

Non-functioning thermostat

1.

Replace thermostat

 

2.

Low gas pressure

2.

Check with gas utility company

 

3.

Non-functioning burner

3.

Replace burner assembly

PILOT FLAME TOO SMALL

1.

Pilot line or orifice clogged

1.

Clean, locate source and correct

 

2.

Low gas pressure

2.

Check with gas utility company

 

3.

Dirty pilot

3.

Clean pilot

26

Page 26
Image 26
Whirlpool SG1J5040T3NOV 7K, 315422-000, W10123251 Problem, Possible Causes, Corrective Action, Pilot Will Not Remain Lit

FAQ

What are some possible causes for the pilot not remaining lit?

Possible causes include air in the gas line, dirt in gas lines, clogged pilot line or orifice, loose thermocouple connection, non-functioning thermocouple, cold drafts, and more.

Why is my water heater experiencing high operation costs?

High operation costs can be caused by a thermostat being set too high, sediment or lime in the tank, having a water heater that is too small for the job, wrong piping connections, leaking faucets, gas leaks, and more.

What should I do if there is a drip from the relief valve?

If there is a drip from the relief valve, it could be due to excessive water pressure, heater stacking, or a closed water system. Use a pressure reducing valve, lower the thermostat setting, or address the closed system/thermal expansion.