Whirlpool E2F30HD035V Temperature and Pressure Relief Valve, Closed System/Thermal Expansion

Models: 140389 140449 121802 E1F50RD045V 140426 140452 140378 E1F20US015V 120V 6510413 140385 140422 140425 E2F50LD045V E2F30HD035V 140403 E2F80HD045V W10123243 E2F50HD045V E2F30LD035V E2F40RD045V E1F12US015V E2F65HD045V E2F40LD045V E2F40HD045V

1 16
Download 16 pages 19.49 Kb
Page 7
Image 7
Closed System/Thermal Expansion

Please note the following:

The system should be installed only with piping that is suitable for potable (drinkable) water such as copper, CPVC, or polybutylene. This water heater must not be installed using iron piping or PVC water piping.

Use only pumps, valves, or fittings that are compatible with potable water.

Use only full flow ball or gate valves. The use of valves that may cause excessive restriction to water flow is not recommended.

Use only 95/5 tin-antimony or other equivalent solder. Any lead based solder must not be used.

Piping that has been treated with chromates, boiler seal, or other chemicals must not be used.

Chemicals that may contaminate the potable water supply must not be added to the piping system.

Closed System/Thermal Expansion

Temperature and Pressure Relief ValveWARNING

Explosion Hazard

If the temperature and pressure relief valve is dripping or leaking, have a qualified person replace it.

Examples of a qualified person include: licensed plumbers, authorized gas company personnel, and authorized service personnel.

Do not plug valve.

Do not remove valve.

Failure to follow these instructions can result in death or explosion.

Periodic discharge of the temperature and pressure relief valve may be due to thermal expansion in a closed water supply system. The water utility supply meter may contain a check valve, backflow preventer or water pressure reducing valve. This will create a closed water system. During

the heating cycle of the water heater, the water expands causing pressure inside the water heater to increase. This may cause the temperature and pressure relief valve to discharge small quantities of hot water. To prevent this, it is recommended that a diaphragm-type expansion tank (suitable for potable water) be installed on the cold water supply line. The expansion tank must have a minimum capacity of 1.5 U.S. gallons for every 50 gallons of stored water. Contact the local water supplier or plumbing inspector for information on other methods to control this situation.

IMPORTANT: Do not plug or remove the temperature and pressure relief valve.

Temperature and Pressure Relief Valve

Manual backgroundWARNING

Explosion Hazard

If the temperature and pressure relief valve is dripping or leaking, have a qualified person replace it.

Examples of a qualified person include: licensed plumbers, authorized gas company personnel, and authorized service personnel.

Do not plug valve.

Do not remove valve.

Failure to follow these instructions can result in death or explosion.

Figure 9

Temperature And Pressure

Relief Valve Installation

Optional Location

Some Models Only

Temperature And

Pressure Valve

Discharge Line

3/4 Inch Min.

Do Not Cap Or Plug

Drain Pan

6 Inch

Maximum

Drain

For protection against excessive pressures and temperatures, a temperature and pressure relief valve must be installed in the opening marked “T & P RELIEF VALVE” (See Figure 9).

CAUTION: To reduce the risk of excessive pressures and temperatures in this water heater, install temperature and pressure relief protective equipment required by local codes, but no less than a combination temperature and pressure relief valve certifi ed by a nationally recognized testing laboratory that maintains periodic inspection of the production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Shutoff

7

Page 7
Image 7
Whirlpool E2F30HD035V, E2F50HD045V, E2F65HD045V Temperature and Pressure Relief Valve, Closed System/Thermal Expansion