Option 1 - Horizontal System

The most common is the horizontal system, in which banks of dryers are all located in one room and vented through a common duct. See the following illustration for an example of a generic horizontal system.

Option 3 - Combination System

The combination system may be used in high-rise apartments, with a bank of dryers installed at several different levels. Each of these banks then exhausts into a central vertical vent. See the following illustration for an example of a combination system.

A

1"*

(25 mm)

A. 4" (102 mm) diameter rigid metal back draft damper

*Minimum spacing required between dryers

Option 2 - Vertical System

The vertical system is used in some apartment buildings that have a washer and dryer on each floor. Each dryer is exhausted into the same central vertical duct. See the following illustration for an example of a generic vertical system.

D

A

F

E

B

C

FF

G

A. 0.6" (15 mm) water column maximum back pressure B. Weighted dampers

C. Individual dryer exhaust - on each floor

D. 0.1" (2.5 mm) water column maximum vacuum E. Main duct

F. Barometric damper (use depends on exhaust system design)

G. Source of outside air

A

E

BC

D

A. Central vertical duct - maximum of 0.1" (2.5 mm) water column vacuum

B. Weighted damper (each dryer)

C. Maximum of 0.6" (15 mm) water column back pressure

D. Barometric damper (use depends on exhaust system design)

E. Outside air source

6

Page 6
Image 6
Whirlpool W10100920C specifications Option 1 Horizontal System, Option 3 Combination System, Option 2 Vertical System