White Rodgers 11B18 Setting The Control, Controls With Adjustable Differential

Models: 11B18

1 6
Download 6 pages 35.82 Kb
Page 3
Image 3
CONTROLS WITH ADJUSTABLE DIFFERENTIAL

CONTROLS WITH ADJUSTABLE DIFFERENTIAL

The movable indicator points to the temperature at which the contacts open. The fixed indicator points to the tem- perature at which the contacts close. The difference between these two indicators is the differential.

To set the control:

1.Use a screwdriver in the adjusting slot (A) on the front of the control to turn the dial so that the fixed indicator

(B) points to the temperature at which the contacts will close.

2.Turn the differential adjusting screw (C) until the movable indicator (D) points to the temperature at which the contacts will open.

“B” Fixed indicator

(cut-in point)

“F” Stop tab

“C” Differential adjusting screw

“D” Movable indicator (cut-out point)

“A” Adjusting

 

slot

“E” Stop screw

ADJUSTABLE DIFFERENTIAL

SETTING THE CONTROL

CONTROLS WITH A FIXED DIFFERENTIAL

The indicator (B) points to the temperature at which the contacts open.

To set the control:

Use a screwdriver in the adjusting slot (A) on the front of the control to rotate dial until the desired tempera- ture at which the contacts will open is positioned directly under the indicator (B).

CONTROLS WITH ADJUSTABLE STOPS

SETTING THE CONTROLCAUTION

Setting stop higher than control being replaced could cause personal injury and/or property dam- age.

1.Loosen stop screw (E) with enclosed wrench.

2.Set dial to original equipment manufacturer's specifi- cation.

3.Without moving the dial, move stop tab (F) against indicator.

4.Retighten stop screw (E).

“F” Stop tab

“B” Fixed

indicator

 

“A” Adjusting

“E” Stop screw

slot

FIXED DIFFERENTIAL

3

Page 3
Image 3
White Rodgers 11B18 Setting The Control, Controls With Adjustable Differential, Controls With A Fixed Differential