CHECK YOUR PROGRAMMING

Follow these steps to check your thermostat programming one final time before beginning thermostat operation.

1.Move SYSTEM switch to HEAT position.

2.Press PRGM to view the 1st weekday heating period time and temperature. Each time you press PRGM, the next heating period time and temperature will be displayed in sequence for weekday, then weekend program periods (you may change any time or temperature during this procedure).

3.Press RUN.

4.Move SYSTEM switch to COOL position.

5.Repeat step 2 to check cooling program.

6.Move SYSTEM switch to HEAT or COOL and press RUN to begin program operation.

YOUR THERMOSTAT IS NOW COMPLETELY PROGRAMMED AND READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!

TROUBLESHOOTING

Reset Operation

If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation you can reset the thermo-

stat by pressing , and TIME at the same time. This also resets the factory defaults to the configuration menu and program. If the thermostat has power, has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.

Batteries

For optimum performance, we recommend replacing batteries once a year with fresh "AA" Energizer® alkaline batteries.

 

 

 

 

 

 

TROUBLESHOOTING

 

 

 

 

 

 

Symptom

 

Possible Cause

 

Corrective Action

 

 

 

 

 

 

 

 

 

NoHeat/No Cool/No Fan

 

1. Blown fuse or tripped circuit breaker.

 

Replace fuse or reset breaker.

(commonproblems)

 

2. Furnace power switch to OFF.

 

Turn switch to ON.

 

 

 

3. Furnace blower compartment door or

 

Replace door panel in proper position to engage

 

 

 

panel loose or not properly installed.

 

safety interlock or door switch.

No Heat

 

1. Pilot light not lit.

 

Re-light pilot.

 

 

 

2. SYSTEMSwitchnotsettoHEAT.

 

Set SYSTEM Switch to Heat and raise setpoint

 

 

 

 

 

aboveroomtemperature.

 

 

 

3. Loose connection to thermostat or system.

 

Verify thermostat and system wires are securely

 

 

 

 

 

attached.

 

 

 

4. Furnace Lock-Out Condition. Heat may also

 

Many furnaces have safety devices that shut the

 

 

 

be intermittent.

 

system down when a lock-out condition occurs.

 

 

 

 

 

If the heat works intermittently contact the furnace

 

 

 

 

 

manufacturer or local service person for assistance.

 

 

 

5. Heating System requires service or

 

Diagonistic: Set SYSTEM Switch toHEAT and raise

 

 

 

thermostat requires replacement.

 

the setpoint above room temperature. Within a few

 

 

 

 

 

seconds the thermostat should make a soft click

 

 

 

 

 

sound. This sound usually indicates the thermostat

 

 

 

 

 

is operating properly. If the thermostat does not

 

 

 

 

 

click, try the reset operation listed above. If the

 

 

 

 

 

thermostat does not click after being reset contact

 

 

 

 

 

your heating and cooling service person or place

 

 

 

 

 

of purchase for a replacement. If the thermostat

 

 

 

 

 

clicks, contact the furnace manufacturer or a

 

 

 

 

 

service person to verify the heating system is

 

 

 

 

 

operating correctly.

 

NoCool

 

1. SYSTEMSwitchnotsettoCOOL

 

SetSYSTEMSwitchtoCOOLandlowersetpoint

 

 

 

 

 

belowroomtemperature.

 

 

 

2. Looseconnectiontothermostatorsystem.

 

Verifythermostatandsystemwiresaresecurely

 

 

 

 

 

attached.

 

 

 

3. Cooling System requires service or thermostat

 

Same procedure as diagnostic for No Heat

 

 

 

requiresreplacement.

 

conditionexceptsetthethermostattoCOOLand

 

 

 

 

 

lower the setpoint below the room temperature.

 

 

 

 

 

There may be up to a five minute delay before

 

 

 

 

 

the thermostat clicks in Cooling if the compressor

 

 

 

 

 

lock-out option is selected in the configuration

 

 

 

 

 

menu (Item 6).

 

 

 

 

 

 

 

7