White Rodgers 1F82-261 specifications Troubleshooting, Symptom, Possible Cause, Corrective Action

Models: 1F82-261

1 8
Download 8 pages 28.6 Kb
Page 8
Image 8
TROUBLESHOOTING

TROUBLESHOOTING

Reset Operation

If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation you can reset the thermo-

stat by pressing the reset button (see Fig 1). If the thermostat has power, has been reset and still does not function correctly contact your heating/cooling service person or place of pur- chase.

Symptom

Possible Cause

Corrective Action

No Heat/No Cool/No Fan

1.

Blown fuse or tripped circuit breaker.

Replace fuse or reset breaker.

(common problems)

2.

Furnace power switch to OFF.

Turn switch to ON.

 

3.

Furnace blower compartment door or

Replace door panel in proper position to engage

 

 

panel loose or not properly installed.

safety interlock or door switch.

No Heat

1.

System Switch not set to Heat.

Set System Switch to Heat and raise setpoint

 

 

 

above room temperature.

 

2.

Loose connection to thermostat or system.

Verify thermostat and system wires are securely

 

 

 

attached.

 

3.

Heating System requires service or

Diagonistic: Set System Switch to Heat and raise

 

 

thermostat requires replacement.

the setpoint above room temperature. Within a five

 

 

 

minutes the thermostat should make a soft click

 

 

 

sound. This sound usually indicates the thermostat

 

 

 

is operating properly. If the thermostat does not

 

 

 

click, try the reset operation listed above. If the

 

 

 

thermostat does not click after being reset contact

 

 

 

your heating and cooling service person or place

 

 

 

of purchase for a replacement. If the thermostat

 

 

 

clicks, contact the furnace manufacturer or a

 

 

 

service person to verify the heating system is

 

 

 

operating correctly.

No Cool

1.

System Switch not set to Cool.

Set System Switch to Cool and lower setpoint

 

 

 

below room temperature.

 

2.

Loose connection to thermostat or system.

Verify thermostat and system wires are securely

 

 

 

attached.

 

3.

Cooling System requires service or thermostat

Same procedure as diagnostic for No Heat

 

 

requires replacement.

condition except set the thermostat to Cool and

 

 

 

lower the setpoint below the room temperature.

 

 

 

There may be up to a five minute delay before

 

 

 

the thermostat clicks in Cooling if the compressor

 

 

 

lock-out option is selected in the configuration

 

 

 

menu (Item 7).

Heat, Cool or Fan Runs Constantly.

1.

Possible short in wiring.

Check each wire connection to verify they are

 

2.

Possible short in thermostat.

not shorted or touching together. No bare wire

 

3.

Possible short in Heat/Cool/Fan system.

should stick out from under terminal screws. Try

 

4.

Fan Switch set to Fan On.

resetting the thermostat as described below.

 

 

 

If the condition persists, the manufacturer of

 

 

 

your system or service person can instruct you

 

 

 

on how to test the Heat/Cool system for correct

 

 

 

operation. If the system operates correctly,

 

 

 

replace the thermostat.

Furnace Cycles Too Fast or Too Slow

1.

The location of the thermostat and/or the size

Item 2 in the Configuration Menu is the adjustment

(narrow or wide temperature swing)

 

of the Heating System may be influencing the

that controls the cycle rate. If an acceptable cycle

 

 

cycle rate.

rate is not achieved using the FA (Fast) or SL

 

 

 

(Slow) adjustment contact a local service person for

 

 

 

additional suggestions.

Cooling Cycles Too Fast or Too Slow

1.

The location of the thermostat and/or the size

The cycle rate for cooling is fixed and can not be

(narrow or wide temperature swing)

 

of the Cooling System may be influencing the

adjusted. Contact a local service person for

 

 

cycle rate.

suggestions.

Thermostat Setting and Thermometer

1.

Thermostat thermometer setting requires

The thermometer can be adjusted +/- 4 degrees as

Disagree

 

adjustment.

listed in item 8 of the Configuration Menu. No other

 

 

 

adjustment is possible.

Clock Loses or Gains Time

1.

Loss of power to thermostat.

The thermostat will maintain its program in memory

 

 

 

even with no power but the clock time will be

 

 

 

incorrect when power is restored. See No

 

 

 

Heat/No Cool/No Fan (common problems) above

 

 

 

for items to check in the system.

Heat or Cool Starts Early

1.

EMR activated

See Configuration Menu (Item 5).

Thermostat Does Not Follow Program

1.

AM or PM set incorrectly in program.

Check current clock and program settings including

 

2.

AM or PM set incorrectly on the clock.

the AM or PM designations for each time period.

 

3.

Voltage spike or static discharge.

If a voltage spike or static discharge occurs use the

 

 

 

Reset Operation listed above.

Blank Display and/or Keypad Not

1.

Voltage Spike or Static Discharge.

If a voltage spike or static discharge occurs use the

Responding

 

 

Reset Operation listed above.

 

 

 

 

Page 8
Image 8
White Rodgers 1F82-261 specifications Troubleshooting, Symptom, Possible Cause, Corrective Action