White Rodgers 1F80ST-0471 Installer/Configuration Menu, To change cycle rate, press the or key

Models: 1F80ST-0471 1F86ST-0471

1 8
Download 8 pages 14.51 Kb
Page 5
Image 5
To change cycle rate, press the  or  key.

INSTALLER/CONFIGURATION MENU

4.Energy Management Recovery: (this step is skipped if confi gured to be non-programmable).

Energy Management Recovery (E) On enables the thermostat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify. Heating will start 5 minutes early for every 1° of temperature required to reach setpoint.

Example: If E On is selected and have your heating programmed to 65° at night and 70° at 7 AM. If the building temperature is 65°, the difference between 65° and 70° is 5°. Allowing 5 minutes per degree, the thermostat setpoint will change to 70° at 6:35 AM. Cooling allows more time per degree, because it takes longer to reach set temperature.

5, 6 & 7. Cycle Rate Selection – The factory default settings with SS/HP switch in SS position for Heat is medium cycle (ME) and Cool is fast cycle (AL). For Heat Pump (HP), the default setting is fast cycle (AL).

To change cycle rate, press the Manual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background or Manual backgroundManual backgroundManual backgroundManual background key.

Cycle rate differentials for different settings are:

MODE

Fast

Medium

Slow

 

 

AL

ME

bA

Heat

(SS)

0.4°F

0.6°F

1.8°F

Cool

(SS)

1.2°F

1.7°F

Heat Pump (HP)

1.2°F

1.7°F

8.Select Compressor Lockout CL OFF or ON – Selecting CL ON will cause the thermostat to wait 5 minutes between cooling cycles. This is intended to help protect the compressor from short cycling. Some newer compressors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs, it will fl ash the setpoint for up to fi ve minutes.

9.System Mode Configuration – This thermostat is confi gured for Calor and Frio with Auto changeover

(SISTEMA switch with Frio Off Calor Auto) default. It can also be confi gured for Calor and Frio (Frio Off Calor), Calor only with fan (Off Calor), Calor only without fan, Auto only (Auto Off), and Frio only (Frio Off).

10.Select Backlight Display – The display backlight improves display contrast in low lighting conditions. When the "C" terminal is powered, selecting backlight L ON will keep the light on continuously. Select backlight OFF will keep the light on momentarily after any key is pressed. When the "C" terminal is not powered, the light will

be on momentarily after any key is pressed no matter whether the backlight is selected ON or OFF.

11.Select Temperature Display Adjustment 4 LO to 4 HI Allows you to adjust the room temperature display up to 4° higher or lower. Your thermostat was accurately calibrated at the factory, but you have the option to change the display temperature to match your previous thermo stat. The current or adjusted room temperature will be displayed on the left side of the display.

12.Select F° or C° Readout – Changes the display readout to Centigrade or Fahrenheit as required.

13.Select Filter Replacement Reminder and Set Run Time Select the "Cambiar Filtro" (Change Filter) reminder On or OFF. If selected On, press MENU to select the time period from 25 to 1975 hours in 25 hours increments.

In a typical system, 200 hours (default) of run time is approximately 30 days. After the selected time of blower operation, the thermostat will display "Cambiar Filtro" (Change Filter) as a reminder to change or clean your air fi lter. When "Cambiar Filtro" (Change Filter) is displayed, press MENU button to clear the display and restart the time to the next fi lter change.

5

Page 5
Image 5
White Rodgers 1F80ST-0471, 1F86ST-0471 specifications Installer/Configuration Menu, To change cycle rate, press the or key