NOTE | ADDITIONAL OPERATION NOTES |
The battery maintains the stored program in the event of a power failure. When attached to the wall with 24 VAC power applied, the thermostat will function normally with- out the battery. However, the program will be lost in the event of power interruption or failure if the battery is not installed. When power is restored, the thermostat will automatically maintain a temperature of 64°F or a cooling temperature of 82°F (factory preprogrammed) as needed.
CHECK THERMOSTAT OPERATION
FAN OPERATION
1.Turn on power to the system. If the heat source has a standing pilot, be sure to light it.
2. | Press | ON - AUTO | until FAN ON is displayed. The blower |
|
| FAN |
|
| should begin to operate. | ||
3. | Press | ON - AUTO | until FAN AUTO is displayed. The |
|
| FAN |
|
blower should stop operating within approximately one minute.
Damper operation is linked to the occupied and unoccu- pied temperature settings, rather than the time settings. The default settings for the damper are:
•The damper is open (energized) for the occupied program.
•The damper is closed
Refer to the OPERATION GUIDE if you need additional information on thermostat operation.
TROUBLESHOOTING
Refer to the Question & Answer section of the OPERA- TION GUIDE for information on troubleshooting the ther- mostat.
HEATING SYSTEM
1. Press SYSTEM until HEAT is displayed (it may already
HEAT - OFF - COOL - AUTO
be displayed).
2.Press to adjust thermostat to 99°F. All stages of the heating system should begin to operate within five minutes.
COOLING SYSTEM
!CAUTION
To prevent compressor and/or property damage, if power to the compressor has been off or inter- rupted for more than 1 hour and the outdoor temperature is below 50°F, DO NOT operate the system for at least the amount of time the com- pressor was off! This will allow the compressor heaters to warm the compressor oils to avoid damage due to slugging.
1. Press | SYSTEM | until COOL is displayed. |
HEAT - OFF - COOL - AUTO |
2.Press to adjust the thermostat to 40°F. All stages of the cooling system should come on within five minutes (if the compressor is not operating, it may be locked out. See LOCKOUT BYPASS OPTION).
LOCKOUT BYPASS OPTION
!CAUTION
FOR QUALIFIED SERVICE TECHNI- CIANS’ USE ONLY. OPERATORS SHOULD NOT USE THIS FEATURE DUE TO POSSIBILITY OF EQUIPMENT OR PROPERTY DAMAGE, OR PERSONAL INJURY.
DO NOT USE THE LOCKOUT BYPASS OPTION UNLESS THE COMPRESSOR OIL HEATERS HAVE BEEN OPERATIONAL FOR 6 HOURS AND THE SYSTEM HAS NOT BEEN OPERATIONAL FOR AT LEAST 5 MINUTES.
COMPRESSOR SHORT TERM
CYCLE PROTECTION
This thermostat has a
while testing thermostat operation, simply press TEMPVIEW
and PRGMVIEW buttons at the same time at initial startup.