24A06G-1

DUAL LEVEL-TEMP

SILENT OPERATOR RELAY

(Normally Open Contacts)

INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.

This Dual Level-Temp Silent Operator Relay is designed for controlling two separate loads with a single low voltage thermostat. It is especially suitable for use with electric heating equipment.

The Dual Level-Temp relay may be used to operate two separate heating loads by means of a single low voltage thermostat. It is equally well suited for use with a heating- cooling thermostat to control heating and cooling loads alter- nately as in motels, apartments, office buildings, etc.

This model Dual Level-Temp relay has a voltage input of 240 volts. Since this relay is equipped with a self-contained trans- former, the supply voltage used must agree with the voltage rating of the relay. This model has both an inductive and non- inductive rating.

DESCRIPTION

The Silent Operator relay has been carefully adjusted at the factory, and no attempt should be made to adjust them in the field.

PRECAUTIONS

If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor, electrician, or someone familiar with basic electricity and wiring.

Do not exceed the specification ratings.

All wiring must conform to local and national electrical codes and ordinances.

This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.

!CAUTION

To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.

!WARNING

Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard.

ELECTRICAL DATA

Switch Action: Two SPST switches, normally open

Thermal: Average time delay – 45 seconds

Ambient Temperature: -20° to 120°F (-24° to 49°C)

Mounting: 1/2" conduit hub or two key slot mounting holes

SPECIFICATIONS

Thermostat Circuit Current:

Bimetal Heater #1 (Red & White Leads) – 0.21 Amps

Bimetal Heater #2 (Red & Black with White Stripe Leads) – 0.21 Amps

 

 

 

 

 

 

ELECTRICAL RATING

 

 

 

 

 

 

 

FOR SWITCH #1

FOR SWITCH #2

 

 

 

TYPE

INPUT

(Red and Black Leads)

(Red Striped and Black Striped Leads)

 

 

 

NUMBER

VOLTAGE /FREQUENCY

NON-INDUCTIVE

INDUCTIVE*

NON-INDUCTIVE

INDUCTIVE*

 

 

 

24A06G-1

240VAC, 60 Hz

25A, 6000W

12 FLA (72 LRA)

25A, 6000W

12 FLA (72 LRA)

 

 

 

*FLA - Full Load Amps.; LRA - Locked Rotor Amps.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

White-Rodgers is a division

 

PART NO. 37-4165C

 

 

 

 

 

of Emerson Electric Co.

 

Replaces 37-4165B

 

 

 

 

 

www.white-rodgers.com

 

0504

 

 

 

 

 

 

Page 1
Image 1
White Rodgers 24A06G-1 specifications Operator Save these instructions for future use, Description, Precautions

24A06G-1 specifications

The White Rodgers 24A06G-1 is a well-regarded thermostat known for its precise temperature control and user-friendly interface. This device is designed to cater to both residential and commercial HVAC systems, streamlining the management of indoor climate while promoting energy efficiency.

One of the standout features of the 24A06G-1 is its compatibility with a wide variety of heating and cooling systems. It is capable of managing both single-stage and multi-stage systems, making it versatile for different applications. This adaptability ensures that users can implement the thermostat into existing systems without hassle, thereby enhancing operational efficiency.

The technology behind the White Rodgers 24A06G-1 incorporates advanced electronic control algorithms that allow for accurate temperature regulation. Users can set their preferred temperatures, and the thermostat will maintain these limits within a narrow range, improving comfort and minimizing energy consumption. Additionally, the unit features an easy-to-read display, making it effortless for users to adjust settings as needed.

Another significant characteristic of the 24A06G-1 is its programmable scheduling capability. Users can set different temperature programs for various times of the day and days of the week, allowing for optimized temperature settings that align with their daily routines. This feature not only enhances comfort but also contributes to energy savings, as it minimizes unnecessary heating or cooling when spaces are unoccupied.

The 24A06G-1 is also equipped with a built-in filter check reminder, ensuring that users are aware when maintenance is required. This proactive reminder helps maintain optimal air quality and system performance. Furthermore, its straightforward installation process requires minimal tools, which is appealing to both professional installers and DIY enthusiasts.

For energy-conscious consumers, the White Rodgers 24A06G-1 provides a reliable solution to manage heating and cooling efficiently. It allows homeowners and businesses to enjoy optimal comfort while keeping energy costs in check. With its comprehensive features, reliable technology, and ease of use, the 24A06G-1 has established itself as a trustworthy option in the thermostat market, catering to a wide range of temperature management needs.