Emerson 37E73A-903, 37E37A-903 & 906, 37E73A-906 installation instructions Troubleshooting

Models: 37E73A-903 37E73A-906 37E37A-903 & 906

1 8
Download 8 pages 15.03 Kb
Page 8
Image 8
www.white-rodgers.com www.emersonclimate.com

TROUBLESHOOTING

A

B

C

7

The self diagnostic test

1. Cycle power to the water heater off for 10 seconds

 

 

 

found a problem with the

and then back on.

 

 

 

 

gas valve driver circuit

2. If the above step did not cleat the error, the

 

 

 

 

 

INTELLI-VENT™ control must be replaced

 

 

 

 

 

 

A

B

C

8

The self diagnostic test has

1. Cycle the external power off for 10 seconds and

detected a problem with

then back on.

 

 

 

 

 

 

 

the internal microcomputer.

2. If the above step does not clear the error, the

 

 

 

 

 

INTELLI-VENT™ control must be replaced.

 

 

 

 

 

 

A

B

C

9

The self diagnostic test has

1. Cycle the external power off for 10 seconds and

detected a problem with

then back on.

 

 

 

 

 

 

 

the internal circuit

2. If the above step does not clear the error, the

 

 

 

 

 

INTELLI-VENTTMcontrol must be replaced.

 

 

 

 

 

 

A

B

C

10

Flame signal sensed out of

1. Replace the INTELLI-VENT™ control.

proper sequence.

 

 

 

 

 

 

 

 

 

 

 

A

B

C

11

The high temperature ther-

1. Replace the INTELLI-VENT™ control.

mal cutoff is open

 

 

 

 

 

 

 

 

 

 

 

A

B

C

12

The diagnostic test has de-

1. Make sure that there are no objects leaning against

tected one of the tempera-

the front of the control.

 

 

 

 

 

 

 

ture adjust buttons stuck

2. Lightly press and release each of the buttons once.

 

 

 

 

closed

3. If the above actions do not clear the error, the

 

 

 

 

 

 

 

 

 

 

control will continue to regulate water temperature

 

 

 

 

 

at the last setting, but you not be able to change

 

 

 

 

 

settings unless you replace the INTELLI-VENT™

 

 

 

 

 

control.

 

 

 

 

 

 

A

B

C

13

The self diagnostic test

1. Check that all wiring is correct and that there are no

has detected that the water

open or shorted circuits.

 

 

 

 

 

 

 

temperature sensor is ei-

2. If no wiring problems are found the INTELLI-VENT™

 

 

 

 

ther open or short circuited.

control must be replaced.

 

 

 

 

 

 

A

B

C

14

The self diagnostic test

1. Check that all wiring is correct and that there are no

found a problem with the

open or shorted circuits.

 

 

 

 

 

 

 

Flammable Vapor Sensor

2. If no wiring problems are found the flammable

 

 

 

 

 

Vapor Sensor must be replaced by qualified service

 

 

 

 

 

person.

 

 

 

 

 

 

A

B

C

15

The control detected the

1. If you smell gas, STOP! Follow the instructions,

presence of flammable

“What to do if you smell gas” on page 1 of this

 

 

 

 

 

 

 

vapors near the appliance

instruction sheet. Otherwise call a qualified service

 

 

 

 

and entered lockout.

person for replacement of the control.

 

 

 

 

 

 