Emerson 37E37A-903 & 906 Sequence Of Operations, Intelli-Vent Sequence of Operation, 1 OR

Models: 37E73A-903 37E73A-906 37E37A-903 & 906

1 8
Download 8 pages 15.03 Kb
Page 6
Image 6
SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS

APPLY POWER TO

APPLIANCE

Intelli-Vent™

Sequence of Operation

 

NO

DISPLAY ERROR CODE

 

 

 

 

 

IS FIELD WIRING

 

 

 

 

 

 

CORRECT?

 

 

1 OR

2

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

REQUEST

NO

 

 

 

 

 

 

 

 

FOR HEAT

 

 

 

 

 

 

 

 

 

PRESENT?

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

IS

NO

WAIT FOR PRESSURE

IS

NO

WAIT FOR PRESSURE

 

 

PRESSURE SWITCH

SWITCH TO OPEN

PRESSURE SWITCH

SWITCH TO OPEN

 

 

PROVEN OPEN WITHIN

 

DISPLAY ERROR

PROVEN OPEN WITHIN

 

DISPLAY ERROR

 

 

5 SECONDS?

 

NUMBER

3

5 SECONDS?

 

NUMBER

3

 

 

YES

 

 

 

YES

 

 

 

 

 

COMBUSTION

 

 

 

COMBUSTION

 

 

 

 

 

BLOWER ON

 

 

 

 

 

 

 

 

 

 

 

BLOWER ON

 

 

 

ONE HOUR AUTO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOCKOUT RESET

 

 

 

 

 

 

 

 

 

DELAY

 

IS

NO

WAIT FOR PRESSURE

IS

NO

WAIT FOR PRESSURE

 

 

PRESSURE SWITCH

PRESSURE SWITCH

 

 

SWITCH TO CLOSE

SWITCH TO CLOSE

 

 

PROVEN CLOSED

 

PROVEN CLOSED

 

 

 

 

DISPLAY ERROR

 

DISPLAY ERROR

 

 

WITHIN 5

 

WITHIN 5

 

 

 

 

NUMBER

4

 

NUMBER

4

 

 

SECONDS?

 

SECONDS?

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PREPURGE

 

 

 

 

 

 

 

 

 

IS

NO

TURN OFF INDUCER

 

 

 

 

 

 

IGNITOR

 

DISPLAY ERROR CODE

 

 

 

 

 

 

OKAY?

 

NUMBER

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TURN OFF INDUCER

 

YES

 

 

 

 

 

 

COMBUSTION

AFTER POST-PURGE

6

 

 

 

 

 

 

DISPLAY ERROR

 

 

 

 

 

 

 

BLOWER OFF

IGNITOR ON FOR

 

 

 

 

WARM-UP TIME

 

 

 

 

MAIN VALVE OPENS

 

 

 

 

YES

 

 

 

INTERPURGE

 

 

 

 

MAIN

 

 

 

 

BURNER LIGHTS

NO

LESS

 

YES

AND IS SENSED

 

MAIN VALVE CLOSES

THAN 3 TRIES

 

DURING TRIAL

 

FOR

 

FOR IGNITION?

 

 

IGNITION

 

 

 

 

YES

 

NO

 

 

IGNITOR TURNS OFF

 

 

 

 

IS

YES

LOST

3

YES

FLAME SENSE

MAIN VALVE CLOSES

LESS THAN

 

LOST?

 

TIMES?

 

 

NO

 

NO

 

 

NO IS REQUEST FOR HEAT

SATISFIED?

YES

MAIN VALVE OFF

COMBUSTION

BLOWER OFF AFTER

POST-PURGE DELAY

Please Note:

The control continually monitors internal circuits and external sensors. Error codes noted above, and those for self-diagnostic faults can be found on pages 8 and 9.

6

Page 6
Image 6
White Rodgers 37E37A-903 & 906, 37E73A-906 Sequence Of Operations, Intelli-Vent Sequence of Operation, Please Note, 1 OR