7 TROUBLESHOOTING

CONTINUED FROM FIFTH PAGE

 

 

 

 

 

Symptom

 

Possible Cause

 

Corrective Action

 

 

 

 

 

 

 

 

No Heat

 

1.

Pilot light not lit.

 

Re-light pilot.

 

 

2.

System Switch not set to HEAT.

 

Set System Switch to HEAT and raise setpoint

 

 

 

 

 

above room temperature.

 

 

3.

Loose connection to thermostat or system.

 

Verify thermostat and system wires are securely

 

 

 

 

 

attached.

 

 

4.

Furnace Lock-Out Condition. Heat may also

 

Many furnaces have safety devices that shut

 

 

 

be intermittent.

 

down when a lock-out condition occurs. If the

 

 

 

 

 

heat works intermittently contact the furnace

 

 

 

 

 

manufacturer or local service person for

 

 

 

 

 

assistance.

 

 

5.

Heating system requires service or

 

Diagnostic: Set System Switch to HEAT and raise

 

 

 

thermostat requires replacement.

 

the setpoint above room temperature. Within a few

 

 

 

 

 

seconds the thermostat should make a soft click

 

 

 

 

 

sound. This sound usually indicates the thermo-

 

 

 

 

 

stat is operating properly. If the thermostat does

 

 

 

 

 

not click, try the reset operation listed above. If the

 

 

 

 

 

thermostat does not click after being reset contact

 

 

 

 

 

your heating and cooling service person or place

 

 

 

 

 

of purchase for a replacement. If the thermostat

 

 

 

 

 

clicks, contact the furnace manufacturer or a

 

 

 

 

 

service person to verify the heating is operating

 

 

 

 

 

correctly.

 

 

 

 

 

 

No Cool

 

1.

System Switch not set to COOL.

 

Set System Switch to COOL and lower setpoint

 

 

 

 

 

below room temperature.

 

 

2.

Loose connection to thermostat or system.

 

Verify thermostat and system wires are securely

 

 

 

 

 

attached.

 

 

3.

Cooling system requires service or

 

Same procedure as diagnostic for No Heat

 

 

 

thermostat requires replacement.

 

condition except set the thermostat to COOL and

 

 

 

 

 

lower the setpoint below the room temperature.

 

 

 

 

 

There may be up to a five minute delay before the

 

 

 

 

 

thermostat clicks in Cooling.

 

 

 

 

 

 

Heat, Cool or Fan Runs Constantly.

 

1.

Possible short in wiring.

 

Check each wire connection to verify they are not

 

 

2.

Possible short in thermostat.

 

shorted or touching together. No bare wire should

 

 

3.

Possible short in heat/cool/fan system.

 

stick out from under terminal screws. Try resetting

 

 

4.

Fan Switch set to Fan On.

 

the thermostat as described above. If the condition

 

 

 

 

 

persists the manufacturer of your system or

 

 

 

 

 

service person can instruct you on how to test the

 

 

 

 

 

Heat/Cool system for correct operation. If the

 

 

 

 

 

system operates correctly, replace the thermostat.

 

 

 

 

 

 

Furnace (Air Conditioning) Cycles Too Fast

 

1.

The location of the thermostat and/or the

 

Digital thermostats normally provide precise

or Too Slow (narrow or wide temperature

 

 

size of the Heating (Cooling) System may

 

temperature control and may cycle faster than

swing)

 

 

be influencing the cycle rate.

 

some older mechanical models. A faster cycle

 

 

 

 

 

rate means the unit turns on and off more

 

 

 

 

 

frequently but runs for a shorter time so there is

 

 

 

 

 

no increase in energy use. If you would like to

 

 

 

 

 

increase the cycle time, clip Jumper W-905 as

 

 

 

 

 

mentioned in the instructions for Hydronic Heating

 

 

 

 

 

Systems. It is not possible to shorten the cycle

 

 

 

 

 

time. If an acceptable cycle rate is not achieved as

 

 

 

 

 

received or by clipping W-905 contact a local

 

 

 

 

 

service person for additional suggestions.

 

 

 

 

 

 

Thermostat Setting and Thermostat

 

1.

Thermostat thermometer setting requires

 

The thermometer can be adjusted +/- 3 degrees.

Thermometer Disagree

 

 

adjustment.

 

See Temperature Display Adjustment in the

 

 

 

 

 

Operation section.

 

 

 

 

 

 

Blank Display and/or Keypad Not

 

1.

Voltage spike or static discharge.

 

Use the Reset Operation listed above.

Responding

 

 

 

 

 

 

 

 

 

 

 

www.white-rodgers.com

Page 6
Image 6
White Rodgers 500 installation instructions From Fifth