C1000AP & C1000APT Airpot Brewer
TROUBLE SHOOTING CONTINUED:
PROBLEM: WATER DOES NOT FLOW INTO HEATING TANK.
POSSIBLE CAUSE | SOLUTION | ||
3. | Grounded probe | When the water level gets below the probe tip, water should automatically refill the tank. | |
|
| If not, pull wire off the probe terminal. Water should now start flowing into the tank. If not, | |
|
| check the water level control board (see step 4) or inlet valve (step 2). | |
|
| ||
4. Defective water level control | Disconnect wire from probe terminal. With a voltmeter, check voltage at the water inlet | ||
| board | coil terminals. This should read | |
|
| control (L.L.C.) board. Make sure the L.L.C. board is supplied by 120V across terminals | |
|
| T2 & T3. The L.L.C. board is grounded to the chassis of the machine by contacting the | |
|
| board to the mounting bracket. Make sure board is grounded here. Check for loose con- | |
|
| nections at terminals. Replace board. | |
|
|
| |
PROBLEM: WATER HEATING TANK OVERFLOWING. | |||
|
| ||
POSSIBLE CAUSE | SOLUTION | ||
1. | Defective water inlet valve | Turn power off and observe water level. If water continues to flow into the heating tank, | |
|
| clean or replace leaky valve. | |
|
|
| |
2. | Probe | Disconnect wire from probe terminal. Touch the body of the heating tank with the | |
|
| terminal at the end of this wire. If water stops, try cleaning the probe. Probe may have | |
|
| to be replaced. | |
|
| ||
3. | Liquid level control board must be securely grounded through the back of the board | ||
| connections at liquid level | and the mounting bracket. Check for loose connections at the terminals. Check for | |
| control board | voltage across the inlet valve terminals. If there is 110 to 120 volts present at the inlet | |
|
| valve terminals when water level is touching the probe tip, replace the L.L.C. board. | |
|
| ||
PROBLEM: WATER IN TANK DOES NOT REACH PROPER TEMPERATURE | |||
|
| ||
POSSIBLE CAUSE | SOLUTION | ||
1. | Thermostat turned OFF | Check thermostat to make sure the shaft is rotated fully clockwise until it stops. | |
| |||
| (or not fully ON). |
| |
|
|
| |
2. | Defective thermostat | Replace thermostat if contacts are open when shaft is fully clockwise and water temper- | |
ature is less than 190º F. You will measure 120 volts (approximately) to ground from both | |||
|
| ||
|
| thermostat terminals when it is ON and from only one terminal when it is OFF. | |
3. | Defective Contactor | Measure the voltage across the coil terminals of the contactor. If you read 110/120V, but | |
|
| ||
|
| the contacts remain open, the coil is burned out. Replace it. | |
|
|
|
[ 4 ]