USING SET AND SEL BUTTONS

Pressing and holding the SET button for five seconds enters the Setup and Advanced Functions modes. The word SEL appears in the display, prompting you to press the SEL button to choose what function you want to SELect.

PRESS BAT 1OR BAT 2TO PICK THE BATTERY YOU WISH TO SET UP.

Pressing SEL chooses a variable or function. The Setup mode always begins at

the (Volts) function. Each press of the SEL button scrolls to the next item. When

a variable or function is selected, its corresponding light and present value is displayed. To change a variable, press the SET button until the value appears that you wish. The order displayed and brief descriptions are below.

LIGHT DESCRIPTION

ChargedVoltage ( Battery must be above this voltage to be considered "full.")

Charged Current % (Charging current in amps must remain below this

percentage of battery capacity to be considered full.)

Battery Capacity in amp hours

Time interval over which current is averaged for Time Remaining function.

Each light will come on in sequence.

Advanced Functions. See page 16.

Locks out SET button and Advanced Func- tions. See page 24.

DisplaysCEF,#CEFRecalc's,AverageDepth of Discharge, Deepest Discharge.

Resets amp hours and allows reset of everything to factory default values. See page 22.

Now let's SET UP your system. We'll explain Charged Voltage, Charged Current Percentage, Battery Capacity, Time of Operation Remaining averaging, and set an appropriate rate compensation (Peukert) exponent.

11