GB
Xpelair Toilet/Bathroom Fans LV100, LV100PC, LV100T, LV100H, LV100HP & LV100PIR installation & operating instructions
Please leave this leaflet with the fan for the benefit of the user
4
Installing the fan
These appliances are intended for connection to fixed wiring.
Check that the electrical rating shown on the transformer matches the mains supply.
THESE APPLIANCES ARE DOUBLE INSULATED AND DO NOT REQUIRE AN EARTH CONNECTION.
All installations must be supervised by a qualified electrician.
Installations and wiring must conform to current IEE Regulations (UK), local or appropriate regulations (other countries).
If you have any queries before installing these products or after they have been installed, call the Xpelair Technical Hotline +44(0) 8709 000430. Our Engineers are there to help you during normal office hours (UK only) and may be faxed at all other times +44(0) 8709 000530.
Customers outside the UK may contact your local Xpelair distributor.
Description
All fans
•Universal mounting kit allows Window/Wall/Panel/Ventilation Shaft/Ceiling mounting options. See termination details. If Ceiling mounting the fan, see section ‘What the installer will need’.
•Single speed extraction.
•12V a.c. operation.
LV100
•Operate the fan using an on/off switch (not supplied).
LV100PC
•Operate the fan using the integral pull cord.
LV100T
•
LV100H
•Operates when triggered automatically by the humidity sensor.
•
LV100HP
•Operates either when triggered automatically by the humidity sensor or when turned on using the integral pull cord switch (light indicates when fan is operating in manual mode).
LV100PIR
•An integral body movement sensor operates the fan as long as movement is detected.
Transformer
•Wall mounted out of reach of bath or shower.
•Provides safety insulated supply for 12V a.c. fan.
What the installer will need
A double pole isolating switch with a minimum contact gap of 3mm (Wall or Ceiling mounted).
If metal switch boxes are used, earthing regulations must be followed.
Suitably rated
Guidelines for maximum cable run between the transformer and fan.
a)Limited to 0.3 volts drop. corresponding to 1.5% reduction in fan performance.
Flexible Fixed
Conductor size mm2 0.75 1.00 | 1.50 2.50 |
Recommended max 4.50 6.00 9.00 15.00 cable
b)Limited to 0.5 volts drop, corresponding to 3% reduction in fan performance.
Flexible Fixed
Conductor size mm2 0.75 1.00 | 1.50 2.50 |
Recommended max. 7.50 10.00 15.00 25.00 cable
•Suitably rated 2 core cable (supply to transformer) LV100, LV100PC, LV100H, LV100HP, LV100PIR.
•Suitably rated 3 core cable (supply to transformer LV100T only.
•3mm Electricians Screwdriver and No.1 or 2 Pozidriv screwdrivers.
•To prevent a possible hazardous situation from water ingress, a condensation trap (Xpelair No. XCT100) must be fitted as close as possible to the fan in all situations where any section of the ductwork is positioned higher than the fan itself.
If wall mounting the fan, you will also need
•Masonry drill, Hammer & Chisel (or Core Drill equipment if available).
•Mortar to make good the hole if required.
If window mounting the fan
•You will need a window pane between 3mm and 6mm thick (preferably 4mm).
•Do not install in glass 3mm thick if the window pane area is more than 0.2 sq.m.
•If installing in sealed double glazing, a specially manufactured unit should be obtained from the glazing manufacturer. You will also require a special kit, Xpelair Cat. ref. DXDG.
•If installing in sash windows, you should mount the fan in the upper window. Secure the upper sash in the closed position and fit stops just below the level of the fan, to prevent damaging it when the sash is raised.
•If installing in a panel which is between 9mm and 46mm thick, you will need a special kit, Xpelair Cat. ref. DXDG. Do not install these fans in panel which is more than 46mm thick.