To install the filters, remove the filter access panel located to the left of the condensate drain connection as shown in Figure 5.

NOTE: Filters must be installed with “Air Flow” arrows pointing inward -- toward the indoor coil. In the event the spacers in the filter section are removed, they must be reinstalled in their origi- nal position.

Slide filters all the way into the filter racks provided. When more than one filter in a filter rack is required, they must butt each other when sliding into position. Replace the filter access panel.

BLOWER ASSEMBLY

Even with good filters properly in place, blower wheels and motors will become dust laden after many months of operation. The entire blower assembly should be inspected annually. If the motor and wheel are heavily coated with dust, they can be brushed and cleaned with a vacuum cleaner.

These units are supplied with blower shaft bearings that do not require maintenance but may be relubri- cated if desired. Every three years, using a low pres- sure grease gun, pump grease into the bearing grease fitting until grease just begins to show at the seals. Do not over lubricate. Use any lithium base grease recom- mended for ball bearing service.

Perform all maintenance operations on the blower motor with electric power disconnected from the unit. Do not attempt to lubricate bearings with the unit in operation.

MOTORS

Outdoor fan motors are permanently lubricated and require no maintenance.

Ventor motor is factory lubricated for an estimated 10 year life.

INDOOR COIL

(2)14" X 20"

FILTERS

CONDENSATE

DRAIN

CONNECTION

(1)14" X 25"

FILTERS

3 - 6 TON UNIT

15TON

(2)18" X 24"

FILTERS

 

20 TON

 

INDOOR COIL

(4) 16" X 20"

 

FILTERS

 

 

 

 

 

CONDENSATE

 

20 TON

DRAIN

 

CONNECTION

 

 

 

 

(4) 16" X 25"

 

FILTERS

 

15 TON

(3)18" X 24"

FILTERS

15 & 20 TON

STANDARD & HIGH EFFICIENCY UNITS

INDOOR COIL

(6) 12" X 24"

FILTERS

CONDENSATE

DRAIN

CONNECTION

(6)12" X 24"

FILTERS

25 TON STANDARD EFFICIENCY

15, 17.5, 20, 25 TON ULTRA-HIGH EFFICIENCY UNITS

FIGURE 5: END VIEW LESS FILTER ACCESS PANEL

Indoor Blower Motor and Drive - The indoor blower motor features ball bearings that do not require peri- odic lubrication. Periodic lubrication of the motor and bearings can extend the life of components but is optional.

If desired, every three years, using a low pressure grease gun, pump grease into the bearing grease fit- ting until grease just begins to show at the seals. Do not over lubricate. Use any lithium base grease recom- mended for ball bearing service.