York BHP024 manual Electrical Data Basic Unit, Unitary Products Group

Models: BHP024

1 28
Download 28 pages 47.21 Kb
Page 16
Image 16

036-21528-003-A-0703

TABLE 15: ELECTRICAL DATA (BASIC UNIT)

 

 

VOLTAGE

 

COMPRESSOR

OUTDOOR

SUPPLY AIR

MINIMUM

MAX

MAX.

UNIT

 

 

 

LIMITATIONS

1

HACR

 

MODEL

POWER

 

 

FAN

BLOWER

FUSE

TRANSFORMER

 

 

 

CIRCUIT

BREAKER

POWER

BHP

SUPPLY

 

 

 

 

 

MOTOR,

MOTOR,

SIZE,

SIZE (VA)

 

 

 

 

 

AMPACITY

SIZE,

FACTOR

 

 

MIN.

MAX.

RLA

LRA

FLA

FLA

AMPS2

 

 

 

 

AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024

208/230-1-60

187

253

 

9.3

57.0

1.1

5.0

17.7

25

25

0.96

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

 

15.0

72.5

1.1

5.0

24.9

35

35

0.96

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

030

208/230-3-60

187

253

 

10.0

63.0

1.1

5.0

18.6

25

25

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460-3-60

414

504

 

5.0

31.0

0.6

5.0

11.9

15

15

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

 

17.2

94.0

1.1

7.3

29.9

45

45

0.96

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

208/230-3-60

187

253

 

11.4

78.0

1.1

7.3

22.7

30

30

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460-3-60

414

504

 

5.7

40.0

0.6

7.3

15.4

20

20

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

 

20.0

104.0

1.1

7.3

33.4

50

50

0.96

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

042

208/230-3-60

187

253

 

13.9

88.0

1.1

7.3

25.8

35

35

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460-3-60

414

504

 

6.4

44.0

0.6

7.3

16.1

20

20

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230-1-60

187

253

 

23.4

126.0

1.5

7.3

38.1

60

60

0.96

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

208/230-3-60

187

253

 

13.0

93.0

1.5

7.3

25.1

35

35

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

460-3-60

414

504

 

6.4

46.5

0.8

7.3

16.3

20

20

0.96

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Rated in accordance with ARI Standard 100, utilization range “A”.

2.Dual element, time delay type.

 

NOMINAL VOLTAGE

VOLTAGE

KW CAP. MULTIPLIER

ELECTRIC HEAT

 

 

 

 

208

0.75

CORRECTION

240

230

0.92

FACTORS

 

 

 

 

 

480

460

0.92

 

 

 

 