York BHP024 manual COOLING CAPACITIES - 5 TON BHP060, Unitary Products Group

Models: BHP024

1 28
Download 28 pages 34.15 Kb
Page 11
Image 11
TABLE 8: COOLING CAPACITIES - 5 TON (BHP060)

036-21528-007-A-1205

TABLE 8: COOLING CAPACITIES - 5 TON (BHP060)

 

 

 

 

 

 

 

 

 

 

 

TEMPERATURE OF AIR ON INDOOR COIL

 

 

 

TEMPERATURE AIR ON

 

 

1600 CFM

 

 

2000 CFM

 

 

OUTDOOR COIL

 

 

 

 

 

WB °F

 

 

 

WB °F

 

 

 

 

 

 

 

 

 

72

67

 

62

57

72

67

 

62

57

 

 

 

NET CAP. MBH

 

64.0

58.5

 

53.4

53.1

64.5

59.0

 

53.8

53.6

 

 

POWER INPUT kW

 

4.62

4.55

 

4.46

4.31

5.08

5.00

 

4.90

4.74

 

CapacitySensible

 

 

 

 

 

86

39.3

48.7

 

53.4

53.1

44.8

55.1

 

53.8

53.6

 

MBH

 

DryEntering

°FBulb

 

83

34.6

44.1

 

52.7

53.1

38.8

49.2

 

53.8

53.6

 

 

 

 

 

 

 

 

 

85 °F

 

1

 

 

 

 

80

30.0

39.4

 

48.0

52.3

32.9

43.2

 

52.6

53.6

 

 

 

 

 

 

 

77

25.3

34.8

 

43.3

47.6

26.9

37.2

 

46.6

47.6

 

 

 

 

 

 

 

74

20.7

30.1

 

38.7

42.9

20.9

31.3

 

40.7

41.6

 

 

 

 

 

 

 

71

--

25.4

 

34.0

38.3

--

25.3

 

34.7

35.7

 

 

 

 

 

 

 

68

--

20.8

 

29.3

33.6

--

19.3

 

28.8

29.7

 

 

 

NET

CAP. MBH

 

 

61.1

55.7

 

50.8

50.2

60.5

55.1

 

50.3

49.7

 

 

POWER INPUT kW

 

5.08

5.01

 

4.89

4.74

5.59

5.51

 

5.37

5.22

 

CapacitySensible

 

 

 

 

 

86

38.1

47.4

 

50.8

50.2

43.4

53.5

 

50.3

49.7

 

MBH

 

DryEntering

°FBulb

 

83

33.5

42.8

 

50.8

50.2

37.4

47.5

 

50.3

49.7

 

 

 

 

 

 

 

 

 

95 °F

 

1

 

 

 

 

80

28.8

38.1

 

46.7

49.4

31.4

41.6

 

50.3

49.7

 

 

 

 

 

 

 

77

24.1

33.4

 

42.0

44.7

25.5

35.6

 

44.4

43.7

 

 

 

 

 

 

 

74

19.5

28.8

 

37.4

40.1

19.5

29.7

 

38.4

37.8

 

 

 

 

 

 

 

71

--

24.1

 

32.7

35.4

--

23.7

 

32.4

31.8

 

 

 

 

 

 

 

68

--

19.4

 

28.0

30.7

--

17.7

 

26.5

25.8

 

 

 

NET

CAP. MBH

 

 

56.9

51.2

 

46.8

47.2

56.3

50.7

 

46.3

46.7

 

 

POWER INPUT kW

 

5.64

5.52

 

5.37

5.28

6.17

6.04

 

5.88

5.77

 

CapacitySensible

 

 

 

 

 

86

36.7

45.7

 

46.8

47.2

41.9

49.9

 

46.3

46.7

 

MBH

 

DryEntering

°FBulb

 

83

32.0

41.1

 

46.8

47.2

35.9

45.9

 

46.3

46.7

 

 

 

 

 

 

 

 

 

105 °F

 

1

 

 

 

 

80

27.3

36.4

 

46.7

46.1

30.0

39.9

 

46.3

46.7

 

 

 

 

 

 

 

77

22.7

31.7

 

42.0

41.5

24.0

34.0

 

40.3

40.7

 

 

 

 

 

 

 

74

18.0

27.1

 

37.3

36.8

18.0

28.0

 

34.4

34.8

 

 

 

 

 

 

 

71

--

22.4

 

32.7

32.1

--

22.0

 

28.4

28.8

 

 

 

 

 

 

 

68

--

17.7

 

28.0

27.5

--

16.1

 

22.4

22.8

 

 

 

NET

CAP. MBH

 

 

52.8

46.8

 

42.7

44.2

52.2

46.2

 

42.3

43.7

 

 

POWER INPUT kW

 

6.20

6.03

 

5.86

5.81

6.76

6.57

 

6.38

6.33

 

CapacitySensible

 

 

 

 

 

86

35.2

44.1

 

42.7

44.2

40.4

46.2

 

42.3

43.7

 

MBH

 

DryEntering

°FBulb

 

83

30.5

39.4

 

42.7

44.2

34.5

44.2

 

42.3

43.7

 

 

 

 

 

 

 

 

 

115 °F

 

1

 

 

 

 

80

25.9

34.7

 

46.6

42.8

28.5

38.3

 

42.3

43.7

 

 

 

 

 

 

 

77

21.2

30.1

 

42.0

38.2

22.5

32.3

 

36.3

37.7

 

 

 

 

 

 

 

74

16.5

25.4

 

37.3

33.5

16.6

26.3

 

30.3

31.8

 

 

 

 

 

 

 

71

--

20.7

 

32.6

28.8

--

20.4

 

24.4

25.8

 

 

 

 

 

 

 

68

--

16.1

 

28.0

24.2

--

14.4

 

18.4

19.8

 

 

 

NET

CAP. MBH

 

 

48.7

42.3

 

38.7

41.2

48.0

41.8

 

38.2

40.7

 

 

POWER INPUT kW

 

6.77

6.54

 

6.34

6.34

7.34

7.10

 

6.89

6.88

 

CapacitySensible

 

 

 

 

 

86

33.7

42.4

 

38.7

41.2

39.0

42.6

 

38.2

40.7

 

MBH

 

DryEntering

°FBulb

 

83

29.1

37.7

 

38.7

41.2

33.0

42.5

 

38.2

40.7

125 °F

 

1

 

 

 

 

80

24.4

33.0

 

46.6

39.5

27.0

36.6

 

38.2

40.7

 

 

 

 

 

 

 

77

19.7

28.4

 

41.9

34.9

21.1

30.6

 

32.3

34.7

 

 

 

 

 

 

 

74

15.1

23.7

 

37.3

30.2

15.1

24.7

 

26.3

28.7

 

 

 

 

 

 

 

71

--

19.0

 

32.6

25.5

--

18.7

 

20.3

22.8

 

 

 

 

 

 

 

68

--

14.4

 

27.9

20.9

--

12.7

 

14.4

16.8

1.These capacities are net capacities - indoor fan heat deducted.

ALL SENSIBLE CAPACITY

Unitary Products Group

11

Page 11
Image 11
York BHP024 manual COOLING CAPACITIES - 5 TON BHP060, Unitary Products Group