TABLE 19: APPLICATION DATA
MODEL |
|
|
|
| BHP |
|
| ||
| 024 | 030 | 036 |
| 042 | 048 | 060 | ||
|
|
|
| ||||||
MINIMUM AIR FLOW |
| COOLING | 800 | 1000 | 1050 |
| 1300 | 1500 | 1500 |
(CFM) |
| HEATING | 800 | 1000 | 1050 |
| 1400 | 1400 | 1500 |
MAXIMUM AIR FLOW |
| COOLING | 900 | 1125 | 1200 |
| 1400 | 1600 | 2050 |
(CFM) |
| HEATING | 900 | 1125 | 1200 |
| 1500 | 1600 | 2050 |
MINIMUM OPERATING TEMPERATURE IN COOLING MODE | 45 | 45 | 45 |
| 45 | 45 | 45 | ||
(AMBIENT, °F) |
|
| |||||||
|
|
|
|
|
|
|
| ||
MIMINIM MIXED AIR IN COOLING MODE |
| 68 / 57 | 68 / 57 | 68 / 57 |
| 68 / 57 | 68 / 57 | 68 / 57 | |
(RETURN AIR, DB °F/WB °F) |
|
| |||||||
|
|
|
|
|
|
|
| ||
MINIMUM MIXED AIR IN HEATING MODE |
| 55 | 55 | 55 |
| 55 | 55 | 55 | |
(RETURN AIR, °F) |
|
| |||||||
|
|
|
|
|
|
|
|
|
| CENTER OF GRAVITY |
|
| D |
FRONT |
| C |
OF | A |
|
UNIT |
| |
|
| |
| B | |
|
| |
26 | ||
| ||
|
|
FIGURE 3 - CENTER OF GRAVITY AND WEIGHTS
CLEARANCES
UNIT CLEARANCES
(MINIMUM)
Front | 12” | |
Back | 0” | |
Left Side (Filter Access) | 24” | |
Right Side | 24” | |
Below Unit1 | 0” | |
Above Unit2 | 36” (For Condenser | |
Air Discharge) | ||
|
1.Units may be installed on combustible floors made from wood or class A, B or C roof covering.
2.Units must be installed outdoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.
NOTE: FOR UNITS APPLIED WITH A ROOF CURB, THE MINIMUM CLE ARANCE MAY BE REDUCED FROM 1 INCH TO 1/2 INCH BETWEEN COMBUSTIBLE ROOF CURB MATERIAL AND THE SUPPLY DUCT.
B1HP | SHIPPING | OPERATING |
| CORNER WEIGHTS |
| |||
UNIT |
|
|
|
|
|
| ||
WEIGHT | WEIGHT | A |
| B | C |
| D | |
SIZE |
|
| ||||||
|
|
|
|
|
|
|
| |
024 | 356 | 351 | 97 |
| 93 | 81 |
| 84 |
030 | 353 | 348 | 96 |
| 93 | 81 |
| 84 |
036 | 388 | 383 | 106 |
| 102 | 89 |
| 92 |
|
|
|
|
|
|
|
|
|
042 | 440 | 435 | 120 |
| 115 | 101 |
| 104 |
|
|
|
|
|
|
|
|
|
048 | 485 | 480 | 132 |
| 127 | 111 |
| 115 |
060 | 495 | 490 | 135 |
| 130 | 113 |
| 117 |
FIGURE 4 - UNIT CLEARANCES
Unitary Products Group | 19 |