Indoor Coil2

 

 

 

 

350154-YTG-C-0808

 

 

 

Additional R-410A Charge / TXV Size for Various Matched Systems

 

 

Outdoor Unit

CZH02411

CZH03611

CZH04811

CZH06011

 

Approved System Thermal Expansion Valve1

1TVM(902/4F1)

1TVM(904/4H1)

1TVM(905/4J1)

1TVM(906/4K1)

Factory Charge, lbs-oz

16 - 2

15 - 14

13 - 8

14 - 1

 

Indoor Coil2

FC/MC/PC32A

FC/MC/PC35B

FC/MC/PC35C

FC/MC/PC37A

FC/MC/PC43B

FC/MC/PC43C

FC/MC/PC48C

FC/MC/PC48D

FC/PC60C

FC/MC/PC60D

FC/MC62D

HC36B

HC42C

HC60D

UC48D

UC60D

AV36C

AV/SV48D

AV/SV60D

F4FV060D

FOOTNOTES:

 

TXV Kit3

- Additional Charge, Oz

 

1

 

0

 

0

 

7

24

 

7

24

 

7

24

 

17

7

 

10

17

7

 

10

 

0

 

0

39

 

15

12

0

 

24

 

 

1

0

17

7

 

10

 

0

7

0

 

 

1

 

0

0

 

1

0

 

 

 

 

 

1Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.

2PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

3A TXV kit must be used with these coils to obtain system performance.

Note: If a TXV is factory installed on the coil, it must be replaced with the listed TXV.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of intercon- necting line tubing.

2.Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.

3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified on the previous page.

4.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evap- orator + adder for line set.

Johnson Controls Unitary Products