MECHANICAL SPECIFICATIONS
GENERAL DESCRIPTION
Units shall be
8.5.They shall have built in field convertible duct con- nections for down discharge supply/return or horizontal discharge supply/return, and be available with factory installed options or field installed accessories.
The units shall be factory wired, piped, charged with R- 22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. Enclosed in each unit shall be a factory test log sheet consisting of the unit tested pressures, temperatures and amps, as tested prior to shipment.
All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI test proce- dures. Units shall be ETL & CGA listed, classified to ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236- M90 conditions.
UNIT CABINET
1.Unit cabinet shall be constructed of G90 galva- nized steel, with exterior surfaces coated with a
2.Indoor blower section shall be insulated with up to 1" thick insulation, coated on the air side. Alumi- num foil faced insulation shall be used in the fur- nace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream.
3.Cabinet panels shall be “large” size, easily remov- able for servicing and maintenance.
4.Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rig- ging and proper sealing on roof curb applications.
5.Disposable 2" filters shall be furnished and be accessible through a removable access door, sealed air tight. Units filter track shall be designed to accommodate either 1" or 2" filters.
6.Fan performance measuring ports shall be pro- vided on the outside of the cabinet to allow accu- rate air measurements of evaporator fan performance without removing panels or creating air
7.Condensate pan shall be internally sloped and conform to ASHARE
8.Unit shall incorporate a fixed outdoor air damper with an outdoor air intake opening covered with a bird screen and a rain hood painted to match the exterior of the unit.
INDOOR (EVAPORATOR) FAN ASSEMBLY
1.Fan shall be a belt drive assembly and include an
2.Fan wheel shall be
3.Bearings shall be sealed and permanently lubri- cated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
1.The outdoor fans shall be of the
2.The 2 outdoor fan motors shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently.
REFRIGERANT COMPONENTS
1.Compressors:
A.Shall be fully hermetic type, direct drive, internally protected with internal
B.Shall have internal spring isolation and sound muf- fling to minimize vibration and noise, and be exter- nally isolated on a dedicated, independent mounting.
2Coils:
A.Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless
Unitary Products Group | 15 |