York DY 036 warranty DY060 / 5 Ton

Models: DY 036

1 36
Download 36 pages 52.71 Kb
Page 12
Image 12

 

 

 

 

 

 

 

 

 

343615-YTG-A-0807

TABLE 12: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT DESCRIPTION / MODEL

 

 

 

DY060 / 5 Ton

 

 

 

 

 

CONFIGURATION

 

 

 

Horizontal Ducted Inlet

 

 

 

 

 

Indoor Blower Speed (RPM)

840

845

1166

1188

 

 

Blower Static Pressure (IWG)

0.2

0.6

0.3

1.3

 

 

Airflow (CFM)

1695

1100

2618

1323

 

 

Blower Motor BHP

0.67

0.50

1.51

0.80

 

 

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

 

Cooling

ID Blower

Cooling

 

 

Octave Center Freq.

Operation2

Operation2

 

Operation2

Operation2

 

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

 

(dB)

Only (dB)

(dB)

 

 

 

 

 

 

 

 

63

77

84

77

84

81

 

85

79

84

 

 

125

71

71

72

73

74

 

75

71

72

 

 

250

57

58

55

56

66

 

66

60

61

 

 

500

53

53

51

51

60

 

60

55

55

 

 

1000

50

50

45

46

60

 

60

53

53

 

 

2000

49

49

43

44

58

 

58

50

50

 

 

4000

49

49

42

43

59

 

59

47

47

 

 

8000

49

49

48

48

54

 

54

47

47

 

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 13: DY060 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

 

 

 

DY060 / 5 Ton

 

 

 

CONFIGURATION

 

 

Horizontal Ducted Discharge

 

 

Indoor Blower Speed (RPM)

840

845

1166

1188

Blower Static Pressure (IWG)

0.2

0.6

0.3

1.3

Airflow (CFM)

1695

1100

2618

1323

Blower Motor BHP

0.67

0.50

1.51

0.80

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

Octave Center Freq.

Operation2

Operation2

Operation2

Operation2

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

 

 

 

 

 

63

82

87

79

88

88

89

82

87

125

75

76

72

74

82

83

78

78

250

69

69

66

66

79

79

73

73

500

64

64

60

60

72

72

66

66

1000

59

60

55

56

68

68

61

61

2000

55

55

50

50

65

65

57

57

4000

58

58

52

52

68

68

60

60

8000

55

55

49

49

66

67

56

56

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

12

Unitary Products Group

Page 12
Image 12
York DY 036 warranty DY060 / 5 Ton

DY 036 specifications

The York DY 036 is a prominent model in the realm of air conditioning systems, particularly known for its efficiency and advanced features. Designed for both residential and commercial applications, the DY 036 stands out due to its exceptional performance and energy savings.

One of the primary features of the York DY 036 is its energy efficiency. With a Seasonal Energy Efficiency Ratio (SEER) rating that exceeds industry standards, this air conditioning unit is engineered to deliver cooling power while minimizing electricity consumption. This makes it an ideal choice for consumers looking to reduce their energy bills without sacrificing comfort.

Equipped with advanced inverter technology, the DY 036 adjusts its cooling output in response to the ambient temperature. This not only enhances comfort by maintaining a consistent indoor climate but also contributes to lower energy use. The inverter system allows the unit to operate at a variable speed, preventing the frequent on-and-off cycling associated with traditional models, which can be a significant energy drain.

Another compelling characteristic of the York DY 036 is its quiet operation. With sound levels kept to a minimum, this model is perfect for installation in environments where noise disturbances are a concern, such as bedrooms or office settings. The use of innovative sound-dampening technology ensures that the system runs unobtrusively, providing comfort without disruptive noise.

The DY 036 also incorporates an advanced filtration system that improves indoor air quality. Its multi-stage filtration process captures dust, allergens, and other pollutants, ensuring a healthier breathing environment for occupants. Regular maintenance is also streamlined with easy-access panels, allowing homeowners and technicians to perform servicing without hassle.

Durability is another hallmark of the York DY 036. Built with high-quality materials and components, it is designed to withstand varying climate conditions, ensuring long-lasting reliability. The unit also boasts advanced corrosion resistance, making it suitable for environments with high humidity or proximity to saltwater.

In summary, the York DY 036 is a cutting-edge air conditioning model that provides energy efficiency, quiet operation, advanced filtration, and durable construction. Whether for residential or commercial use, it represents a blend of comfort, technology, and reliability that meets the demands of modern climate control.