FIGURE 1 - UNIT CUTAWAY

343615-YTG-A-0807

FIGURE 1 - UNIT CUTAWAY

FACTORY-INSTALLED OPTIONS

SINGLE INPUT ELECTRONIC ENTHALPY ECONO- MIZERS - Includes a slide-in /plug-in damper assembly with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in /plug-in damper assembly with a 2-posi- tion, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

PHENOLIC COATED EVAPORATOR AND CON- DENSER COILS - Special coating process that utilizes Technicoat 10-1TMprocesses. Coating is applied by total immersion of the complete coil for maximum protection.

ELECTRIC HEATERS - Wired for single point power supply. These nickel chromium heater elements are pro- vided with limit and automatic reset capability to prevent operation at excessive temperatures.

FILTER OPTIONS - Standard units are shipped with 1” throw-away filters installed. 2” pleated filters are offered as a factory installed option.

CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field.

DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.

BAS - Building Automation System Controls Simplicity® INTELLI-Comfort™ CONTROL - The York® Simplicity® INTELLI-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Out- side Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Con- struction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™ using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventila- tion. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Com- fort Ventilation algorithm to provide comfortable ventilation