ADDITIONAL
OUTDOOR UNIT |
| E4FH018 | E4FH024 | E4FH030 | E4FH036 | E4FH042 | E5FH048 | E4FH060 | |
Orifice in OD Distributor |
| 37 | 45 | 49 | 55 | 65 | 69 | 76 | |
FACTORY CHARGE, LBS. - OZ. |
| 5 - 9 | 5 - 1 | 5 - 12 | 6 - 14 | 8 - 3 | 14 - 0 | ||
ID Orifice included w/Instruction Package |
| 57 | 59 | ||||||
INDOOR COIL |
| COIL ORIFICE1 |
| REQUIRED | SYSTEM ORIFICE + ADDITIONAL CHARGE, OZ. | ||||
G1FA/G1UA024S14, 17 |
| 59 | 57 + 4 | ||||||
G1FA/G1UA030S14 |
| 65 | 57 + 6 | 701 + 0 | 7011 + 0 | ||||
G1FA/G1UA036S14 |
| 73 | 701 + 2 | 7011 + 0 | |||||
G1FA/G1UA036S17 |
| 73 | 7011 + 0 | ||||||
G1FA/G1UA048S17 |
| 84 | |||||||
G1FA/G1UA048S21 |
| 84 | 7021 + 0 | 7021 + 0 | 7031 + 0 | ||||
G1FA/G1UA060S21, 24 |
| 90 | 7021 + 2 | 7021 + 5 | 7031 + 5 | 7031 + 0 | |||
G2FD024S(H)14, 17 |
| 61 | 57 + 6 | 59 + 0 | |||||
G2FD030S(H)17 |
| 65 | 7011 + 8 | 59 + 2 | 7011 + 0 | ||||
GFD035S(H)14 |
| 65 | 59 + 2 | 7011 + 0 | |||||
G2FD036S(H)17 |
| 75 | 7011 + 4 | 7021 + 0 | |||||
G2FD042S(H)21 |
| 78 | 7021 + 2 | 7021 + 0 | |||||
G2FD046S(H)17 |
| 78 | 7021+ 2 | 7021 + 0 | |||||
G2FD048S(H)21, 24 |
| 84 | 7021 + 8 | 7031 + 4 | |||||
G2FD060S(H)24 |
| 90 | 7031 + 5 | 7031 + 0 | |||||
G2FD061SH24 |
| 90 | 7031 + 8 | ||||||
G1HD024 |
| 59 | 59 + 1 | ||||||
G1HD036 |
| 69 | 7011 + 4 | ||||||
G1HD048 |
| 81 | |||||||
G1HD060 |
| 93 | |||||||
F2RP/FP018 |
| (53) | (55) +0 | ||||||
F2RP/FP024 |
| 61 | 57 + 6 | 59 + 0 | |||||
F2RP/FP030 |
| 65 | 59 + 2 | 7011 + 0 | |||||
F2RP/FP036 |
| 75 | 7011 + 4 | 7021 + 0 | |||||
F2RP/FP042 |
| 78 | 7021 + 2 | 7021 + 0 | |||||
F2FP048 |
| 84 | 7021 + 8 | 7031 + 3 | |||||
F2FP060 |
| 90 | 7031 + 5 | 7031 + 0 | |||||
F2FV060 |
| 90 | 7031 + 5 | 7031 + 0 |
FOOTNOTES:
1. Verify the TXV kit and the additional charge required for the specific evaporator coil in the system using the table above.
PROCEDURES:
1.Unit factory charge listed on the unit nameplate includes refigerant for the condenser, the smallest evaporator and for 15 feet of intercon- necting line tubing.
2.Verify the orifice size and the additional charge required for the specific evaporator coil in the system using the table above:
3.Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in the table above.
4.Permanently mark the unit nameplate with the total system charge. Total System Charge=Base Charge (as shipped) +adder for evaporator +adder for line set.
5.If the orifice in the evaporator was changed verify the evaporator nameplate has been marked with the correct orifice size.
Unitary Products Group | 3 |