York E3FB090, E2FB120 Wire Sizing, Refrigerant Piping, General Guidelines, Typical Field Wiring

Models: E3FB090 E2FB120

1 16
Download 16 pages 39.1 Kb
Page 5
Image 5
WIRE SIZING

035-15410-002-B-0404

Both the manual and auto changeover thermostats have non- adjustable, voltage-type anticipators for both cooling and heat- ing.

WIRE SIZING

REFRIGERANT PIPING

GENERAL GUIDELINES

*To determine the total circuit length, add the following distances:

1

- Outdoor Unit to Indoor Unit

____________

2

- Indoor Unit to Thermostat

____________

3

- Thermostat to Indoor Unit

____________

2

- Indoor Unit to Outdoor Unit

____________

 

Total Circuit Length

____________

 

 

 

FIG. 3 - TYPICAL FIELD WIRING

TABLE 3

 

200/230-3-60

0.94 @ 208V

208/230-1-60

 

0.84 @ 230V

 

 

 

 

460-3-60

0.86

460-1-60

 

308/415-3-50

0.86 @ 380V

380/415-1-50

 

0.79 @ 415V

 

 

 

 

208/230-3-60

0.91 @ 208V

208/230-1-60

 

0.82 @ 230V

 

 

 

 

460-3-60

0.82

460-1-60

 

380/415-3-50

0.87 @ 380V

380/415-/-50

 

0.80 @ 415V

 

 

 

1Based on three, 60°C insulated copper conductors in steel conduit. 2Based on a 3% voltage drop.

Unitary Products Group

5

Page 5
Image 5
York E3FB090, E2FB120 installation manual Wire Sizing, Refrigerant Piping, General Guidelines, Typical Field Wiring