036-21315-001 Rev. A (0502)
COOLING CAPACITY - With Air Handler Coils
|
| AIR HANDLER |
| COIL1 |
|
|
| COOLING |
|
| ||
UNIT MODEL |
|
| ELECTRIC 2 |
| RATED | NET MBH |
| SEER | SEER |
| ||
MODEL |
| W | MODEL |
| EER | |||||||
|
| HEAT KW | CFM |
|
|
| W/O TXV | + TXV3 | ||||
|
| TOTAL | SENS. | |||||||||
|
|
|
|
|
| |||||||
|
|
| 1 PH 14 SEER AC WITH |
|
|
|
|
|
| |||
H1RE024S06 | N1AHB0806 |
| 2,5,8,10 | 17 | G2FD036S17 | 800 | 25.2 | 18.1 |
| - | 14.00 | 12.35 |
H1RE030S06 | N1AHB1206 |
| 5,8,10,15,19 | 17 | G2FD036S17 | 1000 | 28.8 | 20.7 |
| - | 13.10 | 11.80 |
| N1AHB1206 |
| 5,8,10,15,19 | 17 | G2FD036S17 | 1200 | 34.0 | 24.5 |
| - | 13.35 | 11.80 |
H1RE036S06 | N1AHB1206 |
| 5,8,10,15,19 | 17 | G2FD046S17 | 1200 | 35.0 | 25.6 |
| - | 14.00 | 12.20 |
N1AHD1406 |
| 5,8,10,15 | 24 | G2FD048S24 | 1200 | 35.4 | 25.7 |
| - | 14.00 | 12.50 | |
|
|
| ||||||||||
| N1AHD1406 |
| 5,8,10,15 | 24 | G2FD060S24 | 1200 | 36.0 | 26.1 |
| - | 14.20 | 12.80 |
| N1AHC1606 |
| 5,8,10,15,20 | 21 | G2FD042S21 | 1400 | 39.0 | 28.2 |
| - | 13.25 | 11.35 |
H2RE042S06 |
|
|
|
|
|
|
|
|
|
|
|
|
N1AHC1606 |
| 5,8,10,15,20 | 21 | G2FD048S21 | 1400 | 39.5 | 28.9 |
| - | 13.50 | 11.60 | |
| N1AHD1406 |
| 5,8,10,15 | 24 | G2FD060S24 | 1400 | 40.5 | 29.6 |
| - | 14.00 | 12.00 |
H2RE048S06 | N1AHD2006 |
| 8,10,15,20,25,30 | 24 | G2FD060S24 | 1600 | 46.5 | 33.9 |
| - | 13.85 | 11.80 |
N1AHD2006 |
| 8,10,15,20,25,30 | 24 | G2FD061H24 | 1600 | 47.0 | 34.3 |
| - | 14.00 | 11.90 | |
|
|
| ||||||||||
H2RE060S06 | N1AHD2006 |
| 8,10,15,20,25,30 | 24 | G2FD060S24 | 1900 | 53.5 | 37.1 |
| - | 13.50 | 12.00 |
N1AHD2006 |
| 8,10,15,20,25,30 | 24 | G2FD061H24 | 2050 | 54.5 | 39.1 |
| - | 13.50 | 12.10 | |
|
|
| ||||||||||
|
|
| 1 PH 14 SEER AC / N1VS - VARIABLE SPEED |
|
|
|
|
| ||||
H1RE024S06 | N1VSB12 |
| 10,15,18 | 17 | G2FD036S17 | 870 | 25.6 | 18.1 |
| - | 15.00 | 13.85 |
N1VSB12 |
| 10,15,18 | 17 | G2FD046S17 | 870 | 26.2 | 18.9 |
| - | 15.50 | 14.15 | |
|
|
| ||||||||||
H1RE030S06 | N1VSB12 |
| 10,15,18 | 17 | G2FD036S17 | 1000 | 29.4 | 20.7 |
| - | 14.50 | 12.95 |
N1VSB12 |
| 10,15,18 | 17 | G2FD046S17 | 1070 | 30.0 | 21.6 |
| - | 15.35 | 13.60 | |
|
|
| ||||||||||
H1RE036S06 | N1VSB12 |
| 10,15,18 | 17 | G2FD046S17 | 1250 | 35.2 | 25.6 |
| - | 14.00 | 12.40 |
N1VSC16 |
| 10,15,18 | 21 | G2FD048S21 | 1285 | 36.0 | 25.7 |
| - | 15.00 | 13.60 | |
|
|
| ||||||||||
| N1VSC16 |
| 10,15,18 | 21 | G2FD048S21 | 1420 | 40.5 | 28.9 |
| - | 14.50 | 12.50 |
H2RE042S06 |
|
|
|
|
|
|
|
|
|
|
|
|
N1VSC16 |
| 10,15,18 | 21 | G2FD048S21 | 1420 | 40.5 | 28.9 |
| - | 14.50 | 12.50 | |
| N1VSD20 |
| 10,15,18,30 | 24 | G2FD060S24 | 1420 | 41.5 | 29.6 |
| - | 15.50 | 13.20 |
H2RE048S06 | N1VSC16 |
| 10,15,18 | 21 | G2FD048S21 | 1590 | 46.0 | 33.2 |
| - | 14.30 | 12.20 |
N1VSD20 |
| 10,15,18,30 | 24 | G2FD060S24 | 1600 | 47.0 | 33.9 |
| - | 14.65 | 12.40 | |
|
|
| ||||||||||
H2RE060S06 | N1VSD20 |
| 8,10,15,20,25,30 | 24 | G2FD060S24 | 1780 | 53.5 | 36.3 |
| - | 13.75 | 12.35 |
N1VSD20 |
| 8,10,15,20,25,30 | 24 | G2FD061H24 | 1780 | 54.5 | 37.0 |
| - | 14.00 | 12.60 | |
|
|
| ||||||||||
|
|
| 1 PH 14 SEER AC / F2RP / RC / FP / FC / FV4,5 |
|
|
|
|
| ||||
H1RE024S06 | F2RP/FP036 |
| 5,8,10,15,19 | 21 | - | 800 | 25.0 | 18.0 |
| - | 13.80 | 12.30 |
F2FP040 |
| 5,8,10,15 | 21 | - | 800 | 25.4 | 17.4 |
| - | 14.00 | 12.75 | |
|
|
| ||||||||||
H1RE030S06 | F2RP/FP036 |
| 5,8,10,15,19 | 21 | - | 1000 | 29.8 | 21.5 |
| - | 13.85 | 12.40 |
F2FP045 |
| 5,8,10,15 | 24 | - | 1000 | 30.6 | 21.5 |
| - | 14.00 | 12.70 | |
|
|
| ||||||||||
| F2RP/FP036 |
| 5,8,10,15,19 | 21 | - | 1200 | 34.4 | 24.8 |
| - | 13.50 | 12.10 |
H1RE036S06 |
|
|
|
|
|
|
|
|
|
|
|
|
F2RP/FP042 |
| 5,8,10,15 | 21 | - | 1200 | 34.4 | 24.8 |
| - | 13.30 | 11.90 | |
| F2FP045 |
| 5,8,10,15 | 24 | - | 1200 | 36.0 | 25.5 |
| - | 14.00 | 12.65 |
H2RE042S06 | F2FP045 |
| 5,8,10,15 | 24 | - | 1400 | 40.5 | 29.8 |
| - | 14.00 | 12.00 |
F2FP048 |
| 5,8,10,15,20,25 | 24 | - | 1400 | 39.5 | 28.9 |
| - | 13.25 | 11.30 | |
|
|
| ||||||||||
H2RE048S06 | F2FP060 |
| 5,8,10,15,20,25 | 24 | - | 1600 | 46.0 | 33.4 |
| - | 13.00 | 11.25 |
F2FV060 |
| 8,10,15,20,25 | 24 | - | 1625 | 47.5 | 34.9 |
| - | 15.50 | 13.20 | |
|
|
| ||||||||||
H2RE060S06 | F2FP060 |
| 10,15,20,25 | 24 | 1900 | 53.0 | 36.7 |
| - | 13.00 | 11.60 | |
F2FV060 |
| 10,15,20,25 | 24 | 1900 | 53.5 | 36.3 |
| - | 13.75 | 12.35 | ||
|
|
|
Rated in accordance with DOE test procedures (Federal Register
KW includes compressor, outdoor fan and indoor blower motor watts.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in
1.G2FD coils available with a factory installed horizontal drain pan. See price pages for specific model number.
2.Single phase units require single phase 2HK heaters.
3.TXV = Use 1TV700 Series Kit.
4.To meet R=4.2 insulation requirements, substitute F2FP for F2RP, and F2FC for F2RC. models. All ratings remain the same.
5.FG8, FG9, and FL8 furnaces and F2RP / F2RC air handlers have B.O.D (Blower on Delay) standard.
- = Not applicable
Unitary Products Group | 3 |