PHYSICAL AND ELECTRICAL DATA

036-21023-005 Rev. A (0802)

PHYSICAL AND ELECTRICAL DATA

MODEL

 

 

H4TS024

H4TS030

H4TS036

H4TS048

H4TS060

UNIT SUPPLY VOLTAGE

 

 

 

 

208/230-1-60

 

 

 

 

 

 

 

 

 

 

NORMAL VOLTAGE RANGE 1

 

 

 

 

187 to 252

 

 

MIN. CIRCUIT AMPACITY

 

 

13.4

15.3

18.6

32.8

35.3

 

 

 

 

 

 

MAX. OVERCURRENT DEVICE AMPS 2

20

25

30

50

60

COMPRESSOR TYPE

 

 

 

 

BRISTOL TS

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR AMPS

 

RATED LOAD

10.3

11.7

13.5

25.7

27.0

 

 

 

 

 

 

 

 

LOCKED ROTOR

64

65

84

135

147

 

 

 

 

 

 

 

 

 

 

 

CRANKCASE HEATER

 

 

YES

YES

YES

YES

YES

 

 

 

 

 

 

 

 

FAN MOTOR AMPS

 

RATED LOAD

.5

.5

.7

.7

1.5

 

 

 

 

 

 

 

 

FAN DIAMETER INCHES

 

 

18

18

24

24

24

 

 

 

 

 

 

 

 

 

 

 

 

RATED HP

1/12

1/12

1/10

1/10

1/4

FAN MOTOR

 

 

 

 

 

 

 

 

NOMINAL RPM

1100

1100

825

825

850

 

 

 

 

 

 

 

 

 

 

 

 

NOMINAL CFM

1850

1850

2800

2800

3200

 

 

 

 

 

 

 

 

 

 

 

FACE AREA SQ. FT

14.2

14.2

20.0

24.0

24.0

COIL

 

 

 

 

 

 

 

 

COIL ROWS DEEP

1

1

1

1

1

 

 

 

 

 

 

 

 

 

 

FIN / INCH

20

20

20

20

20

 

 

 

 

 

 

 

 

 

LIQUID LINE OD

 

 

 

3/8

3/8

3/8

3/8

3/8

 

 

 

 

 

 

 

 

VAPOR LINE OD

 

 

3/4

3/4

7/8

7/8

7/8

 

 

 

 

 

 

 

 

UNIT CHARGE, (LBS - OZ)3

 

 

6 - 0

6 - 4

7 - 0

9 - 12

9 - 2

CHARGE PER FOOT, OZ

 

 

.68

.68

.70

.70

.70

 

 

 

 

 

 

 

 

OPERATING WEIGHT LBS.

 

 

145

145

200

250

252

 

 

 

 

 

 

 

 

 

1Rated in accordance with ARI Standard 110, utilizaton range “A”.

2 Dual element fuses or HACR circuit breaker.

3 The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or sub- tract the amount of refrigerant calculated, using the difference in length multiplied by the per foot value.

48" OVERHEAD

DIMENSIONS

 

 

 

 

CLEARANCE

 

 

 

 

REFRIGERANT

C

UNIT

 

DIMENSIONS

 

 

 

 

CONNECTION

B

MODEL

 

(INCHES)

 

 

 

LINE SIZE

 

 

A 1

 

 

 

 

B

C

Liquid

Vapor

 

024

30-1/8

24

24

 

3/4

 

030

30-1/8

24

24

 

 

 

 

AIR IN

036

31-7/8

35

35

3/8

 

4 SIDES

 

A

048

37-7/8

35

35

 

7/8

 

060

37-7/8

35

35

 

 

5-1/2

VAPOR

CONNECTION2-3/8

LIQUID CONNECTION

3-1/8

2

Unitary Products Group