Table
Problem | Possible Cause | Remedy | |||
|
|
| Airflow blocked or dirty air fil- | Clean or replace air filter. | |
|
|
| ter. | ||
Supply | air | temperature |
| ||
| Check all dampers. Open closed dampers including registers in | ||||
too hot. |
|
| Insufficient airflow. | ||
|
|
| unused rooms. Check system temperature rise. If temperature | ||
|
|
|
| rise is too high, speed up blower fan. | |
|
|
| Excess airflow. | Check system temperature rise. Slow down blower fan if neces- | |
Supply | air | temperature | sary. | ||
| |||||
too cool. |
|
| Excessive duct losses. | Check supply air ductwork. Seal leaky joints and seams. Insu- | |
|
|
| late ductwork if necessary. | ||
|
|
|
| ||
|
|
|
| Increase differential between fan control "fan off" and "fan on" | |
Supply | air | temperature | Fan control "fan on" setting too | settings. (L4064B, L6064A fan / limit controls only, no adjust- | |
low. | ments available for L4064W fan / limit control). Register air de- | ||||
too cool | during first mo- |
| flectors may help. | ||
ments of furnace cycle. |
| ||||
Excessive duct losses. | Check supply air ductwork. Seal leaky joints and seams. Insu- | ||||
|
|
| |||
|
|
| late ductwork if necessary. | ||
|
|
|
|
P4LBX20F19001 ASSEMBLY NOTES
The P4LBX20F19001
1.Remove the crating and packaging materials from each section. Re- move the flue pipe flange gasket packed with the furnace section. The flue pipe gasket will be lying loose on the floor of the furnace sec- tion.
2.Remove the shipping brace from the furnace section flue pipe flange and cabinet. Remove and save all of the screws from the flue pipe flange, and the ten screws from the rear edges of the furnace section cabi- net, (5 per side). The screws will be
3.Place the furnace section and blower section in close proximity. Route the wiring harness from the base of the furnace section through the plastic grommet in the blower section blower division panel.
4.Position and align the flue pipe flange gasket between the furnace section and blower section flue pipe flanges, and hold it in place with a pair of awls or similar tool.
5.Begin fastening the flue pipe flanges together from inside the blower sec- tion to the furnace section with the
28
six
6.Align the screw holes in the blower section blower division panel with the screw holes in the furnace sec- tion cabinet rear edge, from which the ten screws were removed. The screws are started from the inside of the blower section to the furnace section. Tighten all ten screws evenly.
7.In a similar manner, start four of the extra screws removed and saved from the furnace section flue pipe flange into the screw holes along the top of the two furnace sections.
8.Remove the blower motor electric wiring cover plate. Connect the black lead from the wiring harness to motor terminal L1, the white lead to motor terminal L2, and the green lead to the motor casing ground terminal. Position the wires in the motor casing indentations and re- install the blower motor electric wir- ing cover plate.
P3DHX SERIES DOWNFLOW CONFIGURATION NOTES
When the P3DHX12F08001 or P2DHX16F12001 are installed in the downflow configuration on a wooden floor, it should be mounted on a sub- base.
The
Model | |
|
|
|
|
P3DHX12F08001 | 1CB1312 |
|
|
P2DHX16F12001 | 1CB0316 |
If the furnace is to be installed on a wood floor over joists on 12 inch or 16 inch centers, framing modifications are nec- essary.
Rough Size Openings:
P3DHX12F08001: 21” x 21”.
P2DHX16F12001: 22½” x 22½”.
The edges of the rough size opening must be well supported by the joist fram- ing to take the weight of the furnace.
The