413432-YTG-A-0608

Additional R-410A Charge / Orifice Size for Various Matched Systems (Continued)

Outdoor Unit

 

 

TCGF24S41S1

TCGF30S41S1

TCGF36S41S1

TCGF42S41S1

TCGF48S41S1

TCGF60S41S1

Required Orifice or TXV 1

1TVM902

1TVM903

1TVM903

1TVM903

1TVM905

1TVM906

Factory Charge, lbs-oz

3 - 2

3 - 7

3 - 10

4 - 4

4 - 9

5 - 9

 

 

 

 

 

 

 

 

Indoor Coil2,3,4

 

 

Additional Charge, Oz

 

 

F4FP024

 

 

 

0

 

See Caution below

 

 

 

 

 

 

 

 

 

 

F4FP030

 

 

 

3

0

 

See Caution below

 

 

 

 

 

 

 

 

 

 

F4FP036

 

 

 

8

5

 

See Caution below

 

 

 

 

 

 

 

 

 

 

F4FP040

 

 

 

12

8

 

See Caution below

 

 

 

 

 

 

 

 

 

 

F4FP042

 

 

 

8

0

 

See Caution below

 

 

 

 

 

 

 

 

 

 

F4FP045

 

 

 

9

2

 

See Caution below

 

 

 

 

 

 

 

 

 

 

F5FP048

 

 

 

20

10

11

 

See Caution below

 

 

 

 

 

 

 

 

 

 

F5FP060

 

 

 

20

10

11

 

See Caution below

 

 

 

 

 

 

 

 

 

 

F4FV060

 

 

 

9

10

1

 

See Caution below

FOOTNOTES:

1.Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.

2.PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

3.A TXV kit must be used with these coils to obtain system performance. Note: If a TXV is factory installed on the coil, it must be replaced with the listed TXV

4.Refer to Technical Guide for actual system performance for specified matches.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter- connecting line tubing.

2.Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.

3.Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electri- cal Data Table.

4.For TXV match charge weight needs to be weighed in for specififc coil match and lineset length.

5.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.

If the F*FP Air Handler used has a with a factory installed R-22 TXV it MUST BE CHANGED OUT to a R-410A TXV or a orifice for proper operation. If the TXV is not changed out system damage will occur.

4

Johnson Controls Unitary Products

Page 4
Image 4
York TCGF24, TCGF60 warranty Footnotes, Procedures

TCGF60, TCGF24 specifications

The York TCGF24 and TCGF60 are cutting-edge technologies designed to enhance the performance and efficiency of air conditioning systems. These units have gained significant popularity due to their advanced features, reliable performance, and energy-saving capabilities.

The TCGF24 and TCGF60 models are part of York's renowned line of commercial cooling products, designed primarily for larger spaces requiring consistent climate control. One of the standout features of these models is their powerful cooling capacity. The TCGF24 offers a cooling capacity of 24 tons, while the TCGF60 boasts an impressive 60 tons, making them suitable for a wide range of applications, from office buildings to industrial facilities.

Efficiency is a crucial consideration in today’s HVAC systems, and York has incorporated several technologies to ensure that both the TCGF24 and TCGF60 deliver optimal performance with reduced energy consumption. They utilize scroll compressors, which are known for their reliability and efficiency, helping to minimize energy costs. The units also come with advanced variable speed drive technology, allowing them to adjust motor speeds based on the cooling demands, further enhancing energy efficiency.

Both models are designed with user-friendliness in mind. They are equipped with intuitive control systems that simplify operation and monitoring. Building management systems can easily interface with these units, providing real-time data on performance and energy use. This feature allows facility managers to proactively manage the cooling system, ensuring that it operates at peak performance while adhering to sustainability goals.

In addition to performance and efficiency, durability is a key characteristic of the TCGF24 and TCGF60. Constructed with high-quality materials, these units are designed to withstand challenging environmental conditions. They come with robust insulation and weatherproof casings, ensuring longevity and reliable operation even in demanding situations.

The York TCGF24 and TCGF60 are also designed with environmental considerations in mind. They use refrigerants that have a lower global warming potential, aligning with modern regulations and sustainability initiatives. This focus on eco-friendly solutions further solidifies York's commitment to innovation in the HVAC industry.

In conclusion, the York TCGF24 and TCGF60 stand out as superior choices for commercial cooling solutions. With their advanced technologies, energy efficiency, user-friendly design, and enhanced durability, they offer reliable performance that meets the demands of today's commercial environments while also prioritizing environmental responsibility. These models exemplify York's dedication to providing innovative HVAC solutions that cater to both efficiency and sustainability.