364834-YTG-C-0708

Physical and Electrical Data

MODEL

 

YCJD18

YCJD24

YCJD30

 

YCJD36

 

YCJD42

YCJD48

YCJD60

 

S41S1(H)

S41S1(H)

S41S1(H)

 

S41S1(H)

 

S41S1(H)

S41S1(H)

S41S1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Supply Voltage

 

 

 

208-230V, 1φ, 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

Normal Voltage Range 1

 

 

 

 

187 to 252

 

 

 

Minimum Circuit Ampacity

10.0

12.4

14.7

 

17.9

 

21.5

21.1

34.3

 

 

 

 

 

 

 

 

 

 

Max. Overcurrent Device Amps 2

15

20

25

 

30

 

35

35

60

Min. Overcurrent Device Amps 3

15

15

15

 

20

 

25

25

35

Compressor Type

 

Rotary

Recip

Recip

 

Recip

 

Recip

Recip

Scroll

 

 

 

 

 

 

 

 

 

 

 

Compressor Amps

Rated Load

7.6

9.3

10.6

 

13.1

 

16.0

15.7

26.2

 

 

 

 

 

 

 

 

 

 

Locked Rotor

40.0

43.0

54.0

 

74

 

84

84

150

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

No

No

No

 

No

 

No

No

No

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Amps

Rated Load

0.5

0.8

1.4

 

1.5

 

1.5

1.5

1.5

 

 

 

 

 

 

 

 

 

 

 

Fan Diameter Inches

17.5

17.5

17.5

 

22

 

22

22

24

 

 

 

 

 

 

 

 

 

 

 

 

Rated HP

1/12

1/8

1/4

 

1/4

 

1/4

1/4

1/4

Fan Motor

 

 

 

 

 

 

 

 

 

 

Nominal RPM

1100

1075

1100

 

850

 

850

850

850

 

 

 

 

 

 

 

 

 

 

 

 

Nominal CFM

1400

1950

2050

 

3200

 

2950

2950

3600

 

 

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

9.60

9.60

9.60

 

13.07

 

14.16

14.16

18.68

Coil

 

 

 

 

 

 

 

 

 

 

Rows Deep

1

1

1

 

1

 

1

1

1

 

 

 

 

 

 

 

 

 

 

 

 

Fin / Inches

23

23

23

 

23

 

23

23

23

 

 

 

 

 

 

 

 

 

 

 

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

 

3/8

 

3/8

3/8

3/8

 

 

 

 

 

 

 

 

 

 

Vapor Line Set OD (Field Installed)

5/8

3/4

3/4

 

3/4

 

7/8

7/8

7/8

 

 

 

 

 

 

 

 

 

 

Unit Charge (Lbs. - Oz.) 4

3 - 3

3 - 13

3 - 14

 

4 - 9

 

4 - 5

4 - 9

5 - 6

Charge Per Foot, Oz.

0.58

0.62

0.62

 

0.62

 

0.67

0.67

0.67

 

 

 

 

 

 

 

 

 

 

Operating Weight Lbs.

97

129

131

 

145

 

173

173

195

 

 

 

 

 

 

 

 

 

 

 

Models with “H” on the end of the model number have a factory installed start kits.

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

 

 

All dimensions are in inches. They are subject to change

 

 

without notice. Certified dimensions will be provided upon

 

C

request.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

Dimensions

 

Refrigerant Connection

 

 

 

 

 

(Inches)

 

 

Service Valve Size

 

 

 

 

 

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

A1

 

B

 

C

Liquid

Vapor

 

 

 

 

 

 

 

 

 

18

28

 

23-1/2

23-1/2

 

 

 

 

 

 

 

 

 

 

 

 

A

 

24

28

 

23-1/2

23-1/2

 

3/4”

 

30

28

 

23-1/2

23-1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/8”

 

 

 

 

36

28

 

29

 

29

 

 

 

 

42

30

 

29

 

29

 

 

 

 

 

48

30

 

29

 

29

 

7/8”

 

 

 

60

32

 

33-5/8

33-5/8

 

 

B

1. Including Fan Guard.

 

2

Johnson Controls Unitary Products

Page 2
Image 2
York warranty Model, YCJD18 YCJD24 YCJD30 YCJD36 YCJD42 YCJD48 YCJD60