York YHJF18 warranty Typical Installation, Typical Field Wiring, YTG-A-0409

Models: YHJF18

1 26
Download 26 pages 38.27 Kb
Page 11
Image 11
TYPICAL INSTALLATION

510667-YTG-A-0409

SOUND LEVEL - TYPICAL OCTAVE BAND SPECTRUM (without tone adjustment)

Size

Test Condition

63

125

250

500

1000

2000

4000

8000

dBA

SQI

RSS Sound Power Calibration 1091 402

82.8

85.4

85.9

85.3

88.1

88.6

86.6

83.9

18

Cooling Mode

67.3

69.2

64.6

67.3

65.5

61.5

58.2

51.8

70.0

19.21

Heating Mode

68.9

69.0

64.0

66.4

66.6

59.6

56.4

52.6

69.7

19.17

 

24

Cooling Mode

70.0

73.6

64.0

70.0

71.8

63.2

57.3

52.3

73.9

19.19

Heating Mode

72.2

71.0

68.5

74.1

71.9

63.4

59.8

53.4

75.4

19.14

 

30

Cooling Mode

70.5

68.8

64.3

65.3

65.5

60.3

55.8

50.6

69.0

19.01

Heating Mode

72.2

70.1

67.5

66.7

69.4

62.5

58.3

52.7

72.0

19.03

 

36

Cooling Mode

70.9

69.3

65.3

66.4

66.3

59.7

56.7

50.8

69.6

19.14

Heating Mode

73.2

70.1

66.9

68.5

68.4

61.6

59.4

55.5

71.7

19.12

 

42

Cooling Mode

71.7

69.5

72.1

69.0

71.3

60.6

56.9

54.0

73.3

19.01

Heating Mode

72.6

72.6

68.1

70.5

70.9

62.7

59.2

56.9

73.6

19.02

 

48

Cooling Mode

71.0

71.0

68.4

68.1

67.9

60.1

55.8

51.3

70.8

19.11

Heating Mode

73.6

72.5

74.0

73.6

75.8

64.0

63.2

56.8

77.6

19.08

 

60

Cooling Mode - High Stage

71.2

69.4

71.4

73.2

71.2

61.1

57.6

52.8

74.7

19.09

Heating Mode - High Stage

71.6

72.7

69.6

71.3

72.4

63.4

61.5

57.4

75.0

19.05

 

* Rated in accordance with ARI 270-2008 Standards.

TYPICAL INSTALLATION

 

MINIMUM 24” SERVICE

 

48” OVERHEAD

ACCESS CLEARANCE

THERMOSTAT

ON ONE SIDE

CLEARANCE

 

 

 

 

WEATHERPROOF

 

 

DISCONNECT

 

 

SWITCH

 

 

 

NEC CLASS 1 WIRING

10” CLEARANCE

 

TO FURNACE OR

AROUND PERIMETER

 

AIR HANDLER

 

 

TERMINAL BLOCK

 

 

NEC CLASS 2 WIRING

 

 

TO INDOOR COIL

NOTE:

 

 

ALL OUTDOOR WIRING

CONTROL

 

MUST BE WEATHERPROOF.

 

ACCESS

SEAL OPENING(S) WITH

 

 

PANEL

PERMAGUM OR EQUIVALENT

TYPICAL FIELD WIRING

ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES

THERMOSTAT

R

B or C

Y

O

W

L or X

G

 

 

1 FIELD

2

T

INSTALLED

2

JUMPER

E

1 JUMPER TERMINALS E AND W TO HEAT

ON FIRST STAGE DURING EMERGENCY HEAT.

INDOOR UNIT

LOW VOLTAGE TERMINAL BLOCK 3,4 IN AIR HANDLER WITH ELECTRIC HEAT

R

C

Y

O

W2

GTYPICAL FIELD WIRING

W1

BK Manual backgroundManual backgroundManual background

DEHUMIDIFICATION CONTROL CONNECTION (Humidistat* Jumper must be removed)

OUTDOOR UNIT

DEFROST

CONTROL

RED

R

 

 

 

CONTACTOR

BLK

 

C

 

 

 

 

 

YEL

Y

T2

T1

 

 

 

ORG

O

 

M

 

 

 

BRN

W

L2

L1

 

PUR X/L

 

 

WHT W1/66

 

 

5GRY CC

 

 

GND.

SCREW

2 TERMINAL NOT USED ON ALL THERMOSTATS.

POWER WIRING

24V CONTROL WIRING (NEC CLASS 2)

GND.

LUG

CIRCUIT BREAKER***

POWER WIRING

208/230-1-60

230-1-50

3CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS.

4CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER. 5GRAY FOR USE WITH OPTIONAL OUTDOOR THERMOSTAT KITS.

Johnson Controls Unitary Products

11

Page 11
Image 11
York YHJF18 warranty Typical Installation, Typical Field Wiring, YTG-A-0409, Johnson Controls Unitary Products