FILTER PERFORMANCE
The airflow capacity data published in the “Blower Perfor- mance” table represents blower performance WITHOUT filters.
All applications of these furnaces require the use of field installed air filters. All filter media and mounting hardware or provisions must be field installed external to the furnace cabi- net. DO NOT attempt to install any filters inside the furnace.
NOTE: Single side return above 1800 CFM is approved as long as the filter velocity does not exceed filter manufacturer’s rec- ommendation and a transition is used to allow use of a 20 x 25 filter.
Recommended Filter Sizes
CFM | Cabinet | Side | Bottom | |
Size | (in) | (in) | ||
| ||||
|
|
|
| |
1200 | B | 16 x 25 | 16 x 25 | |
|
|
|
| |
1600 | C | 16 x 25 | 20 x 25 | |
|
|
|
| |
2000 | C | (2) 16 x 25 | 20 x 25 | |
|
|
|
| |
2000 | D | (2) 16 x 25 | 22 x 25 | |
|
|
|
|
NOTES:
1.Air velocity through throwaway type filters may not exceed 300 feet per min- ute (91.4 m/min). All velocities over this require the use of high velocity fil- ters.
2.Do not exceed 1800 CFM using a single side return and a 16x25 filter. For CFM greater than 1800, you may use two side returns or one side and the bottom or one return with a transition to allow use of a 20x25 filter.
Unit Clearances to Combustibles
Application | Upflow | Downflow | Horizontal |
Top | 1" | 0" | 0" |
Vent | 0" | 0" | 0" |
Rear | 0" | 0" | 0" |
Side | 0" | 0" | 1" |
Front1 | 0" | 0" | 0" |
Floor | Combustible | Combustible2 | Combustible |
Closet | Yes | Yes | Yes |
|
|
|
|
Line Contact | No | No | Yes |
|
|
|
|
1.Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace jacket and building joists, studs or framing.
2.For combustible floors only when used with special
All furnaces approved for alcove and attic installation.
ACCESSORIES
Propane (LP) Conversion Kit -
1NP0681 - All Models
This accessory conversion kit may be used to convert natural gas (N) units for propane (LP) operation.
Do not use Conversion Kit
Concentric Vent Termination -
For use through rooftop, sidewall. Allows combustion air to enter and exhaust to exit through single common hole. Elimi- nates unslightly elbows for a cleaner installation.
Johnson Controls Unitary Products
538513-
Sidewall Vent Termination Kit -
For use on sidewall,
Condensate Neutralizer Kit -
1NK0301
Neutralizer cartridge has a 1/2" plastic tube fittings for installa- tion in the drain line. Calcium carbonate refill media is also available from the Source 1 Parts (p/n
Side Return Filter Racks -
1SR0200 - All Models
1SR0402 - All Models
1SF0101 - All Models
Bottom Return Filter Racks -
1BR0517 or 1BR0617 - For
1BR05xx series are galvanized steel filter racks. 1BR06xx are
Combustible Floor Base Kit -
For installation of these furnaces in downflow applications directly onto combustible flooring material, These kits are required to prevent potential overheating situations. These kits are also required in any applications where the furnace in installed in a downflow configuration without an evaporator coil, where the combustible floor base kit provides access for com- bustible airflow.
1CB0517 - For
EAC Transition Kits -
For installation of EAC accessories with these furnaces to pro- vide easy transition of return airflow through the EAC to get the proper sealing and reduced airflow leakage.
1TK1001 - For all models using side return 1TK1017 - For
High Altitude - No high altitude kits are required.
Thermostats - Compatible thermostat controls are available through accessory sourcing. For optimum performance and installation, refer to the UPGNET “Low Voltage Wiring Diagram” document to select and apply controls.