Omega ILD44-UTP, ILD24-UTP manual Start Auto Tune PID, Proportional Band Submenu

Page 44

If Anti Integral (Anti Windup) Submenu “Enabled”, this feature allows the error term outside the proportional band to be calculated and accumulated for integration. This may be an important feature in applications where fast response time is desirable.

START AUTO TUNE PID:

Press d 27) Display flashes ENBL or DSBL.

Press b 28) Scroll through the available selections: “Enable” or “Disable”. Press d 29) Display shows STRD stored message momentarily and then advances to CYCL only, if it was changed, otherwise press a to

advance to CYCL Cycle Time Submenu.

If “Enabled”, the controller is ready to calculate P, PI or PID parameters. The instrument performs this by activating the output and observing the delay and rate at which the Process Value changes. The setpoints must be at least 18°F or 10°C above the (PV) Process Value in order to perform Auto Tune, otherwise an error message will be displayed.

To start Auto Tune PlD select PID, enable Auto PID and enable Start PID. Sometimes Auto PID parameter needs fine tuning i.e. for each 5°F over shoot increase the Proportional Band (PB) by 15% and for each ±1°F fluctuation at the Setpoint (SP) increase reset by 20%.

Once started, display shows A.TUN with letters blinking in the rotating pattern. When auto tune stops, display will show process value. Do not perform any operations or settings before first stopping Auto Tune. Any alarms or other output is disabled during Auto Tune.

If “AUTO PID” was “DISABLED”, the display will show the following three submenus. This allows the user to manually enter values for Proportional, Reset and Rate terms corresponding to P, I, and D. It also can be used for auto PID for disabling unwanted parameter i.e. PI enter 0000 for rate.

PROPORTIONAL BAND SUBMENU:

Press d 30) Display flashes 1st digit of the previous P PRoP Proportional band value.

Press b & c 31) Press b and c buttons to enter a new “Proportional Band” value.

Press d 32) Display shows STRD stored message momentarily and then advances to REST only, if it was changed, otherwise press a to advance to REST Reset Setup Submenu.

Proportional band is in degrees of temperature or counts of process. Proportional band is defined, as the change in the instrument input to cause a 100% change in the controller output.

40

Image 44
Contents User’s Guide Servicing North America Table of Contents List of Figures List of TablesTIP Part Introduction DescriptionSafety Considerations EMC ConsiderationsBefore You Begin Part Setup MountingMounting iLD Big Display on Bail Front Panel AnnunciatorsMounting iLD Big Display Through Panel Power Rear Panel ConnectionsInput OptionElectrical Installation Power Connections Main Power ConnectionsThermocouple Wiring Hookup TC Wire Color Chart Thermocouple3 Two/Three/Four-Wire RTD Without Sensor Excitation Process CurrentProcess Voltage Outputs Wiring Hookup Wiring OutputsRS-232 Output Wiring Hookup b RS-485 Output Wiring Hookup 12 Excitation Output Operation Configuration Mode Introduction Button Function in Configuration ModePart Turning your Controller On for the First TimeMenu Configuration Flow Chart for ID and SetpointsID Number Entering Your NON-DEFAULT Full Security ID NumberEntering Your NON-DEFAULT SETPOINT/ID Security ID Number Set Points SetpointInput Type Menu Configuration MenuEnter Configuration Menu Input Type Thermocouple Enter Input Type MenuThermocouple Submenu Thermocouple TypesInput Type RTD RTD SubmenuRTD Types RTD Value SubmenuReading Configuration Input Type ProcessProcess Submenu Process TypesEnter Reading Configuration Menu Temperature Unit SubmenuDecimal Point Submenu Filter Constant SubmenuReading Configuration If Process was selected INPUT/READING Scale and Offset SubmenuConversion Table Range Conversion NumberAlarm Enter Alarm 1 MenuAlarm 1 LATCH/UNLATCH Submenu Alarm 1 ENABLE/DISABLE SubmenuAlarm 1 ABSOLUTE/DEVIATION Submenu Contact Closure Submenu Active SubmenuAlarm 1 HI Value Submenu Alarm ENABLE/DISABLE AT Power onAlarm 1 LOW Value Submenu Analog Output Retransmission Enter Analog Output MenuAnalog Output ENABLE/DISABLE Submenu CURRENT/VOLTAGE SubmenuReading OUTFor example Enter Alarm 2 Menu Alarm 2 ENABLE/DISABLE Submenu Loop Break ENABLE/DISABLE SubmenuLoop Break Time Enter Loop Break Time MenuLoop Break Time Value Submenu Reading Adjust SubmenuSetpoint Deviation ENABLE/DISABLE Submenu Thermocouple Field Calibration Submenu Flow Chart for Output OutputMINIMUM/PERCENT LOW Submenu Enter Output 1 MenuSelf Submenu MAXIMUM/PERCENT High Submenu Control Type OutputAnti Integral Submenu Action Type SubmenuAuto PID Submenu Start Auto Tune PID Proportional Band SubmenuCycle Time Submenu Reset Setup SubmenuRate Setup Submenu Damping Factor Submenu Deadband SubmenuEnter Output 2 Menu Control Type SubmenuAction Type Submenu Cycle Time Submenu Ramp ENABLE/DISABLE Submenu Soak ENABLE/DISABLE SubmenuRamp & Soak Enter Ramp and Soak MenuRamp Value Submenu Soak Value SubmenuEnter ID Code Menu Entering or Changing Your NON-DEFAULT ID CodeID Code SETPOINT/ID Security Level Submenu Entering or Changing Your Default ID CodeFull Security Level Submenu 13 Flow Chart for Communication Option Communication OptionEnter Communication Option Menu Communication Parameters SubmenuBaud Submenu Parity SubmenuStop BIT Submenu BUS Format SubmenuModbus Protocol Submenu Line Feed SubmenuData Separation Character Submenu Data Flow Mode SubmenuCommunication Interface Standard Submenu Alarm Status Submenu Data Format SubmenuMain Reading Submenu Peak Value SubmenuAddress Setup Submenu Address Value SubmenuTransmit Time Interval Submenu Transmit Time Interval Value SubmenuAlarm 1 Display Color Submenu Display Color SelectionEnter Display Color Selection Menu Normal Color Display SubmenuAlarm 2 Display Color Submenu ExampleDisplay Colors change sequences Green RED AmberRED Green Part Specifications NmrrCmrr ControlControl Output 1 SSRInsulation GeneralInput Properties Input Type Range AccuracyPart Factory Preset Values Factory preset valueMenu Items Factory Preset Values Notes CE Approval Information Page WARRANTY/DISCLAIMER Return REQUESTS/INQUIRIESTemperature PRESSURE, Strain and ForceFLOW/LEVEL Data Acquisition
Related manuals
Manual 2 pages 47.34 Kb

ILD24-UTP, ILD44-UTP specifications

The Omega ILD44-UTP and ILD24-UTP are advanced intrusion detection sensors designed for versatile security applications. These devices stand out due to their cutting-edge technology, ensuring reliability and high performance in safeguarding various environments.

One of the primary features of the ILD44-UTP and ILD24-UTP is their unique dual-tech detection capability. By utilizing both passive infrared (PIR) and microwave detection, these sensors significantly reduce false alarms while ensuring accurate intrusion detection. The combination of these technologies allows for effective monitoring in different settings, including residential, commercial, and industrial spaces.

The ILD44-UTP model is equipped with a wider detection range compared to its counterpart, the ILD24-UTP. It is capable of covering a detection area of up to 44 meters, making it ideal for larger spaces. Conversely, the ILD24-UTP provides effective coverage for smaller areas, reaching up to 24 meters. This range flexibility gives users the option to select a model that best fits their particular needs.

Another important characteristic is the sensor's weather-resistant design, which allows it to be installed outdoors without compromising performance. The ILD44-UTP and ILD24-UTP are rated for various environmental conditions, ensuring they remain operational in rain, snow, or extreme temperatures. This durability makes them suitable for use on building perimeters, parking lots, and other outdoor security applications.

Both models are equipped with advanced signal processing algorithms that enhance their ability to differentiate between real threats and environmental disturbances, greatly minimizing false alarm rates. This feature is especially critical in settings where frequent alarms can lead to alarm fatigue among security personnel.

The installation process for both devices is straightforward, with user-friendly mounting options. They can be easily integrated into existing security systems, offering flexibility for users to combine them with other security measures such as cameras and access control systems.

Additionally, the ILD44-UTP and ILD24-UTP come with various output options, including relay and voltage outputs, enabling seamless integration with alarm systems and monitoring solutions. Their compatibility with different protocols ensures they can be tied into a wide array of security infrastructures.

Overall, the Omega ILD44-UTP and ILD24-UTP sensors represent a significant advancement in intrusion detection technology, combining robust performance with innovative features that cater to a variety of security needs. Their versatility, durability, and reliability position them as top choices for enhancing security across numerous applications.