Roberts Gorden 300, 200, 350, 150, 400, 175, 225 250 National Standards and Applicable Codes

Page 11

SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES

SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES

4.1 Gas Codes

The type of gas appearing on the name plate must be the type of gas used. Installation must comply with national and local codes and requirements of the local gas company.

United States: Refer to NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code.

Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.

4.2 Aircraft Hangars

Installation in aircraft hangars must be in accordance with the following codes:

United States: Refer to Standard for Aircraft Hangars, NFPA 409 - latest revision.

Canada: Refer to Standard CSA B149.1 Natural Gas and Propane Installation Code.

In aircraft storage and servicing areas, heaters shall be installed at least 10' (3 m) above the upper surface of wings or of engine enclosures of the highest aircraft which may be housed in the hangar. The measurement shall be made from the wing or engine enclosure (whichever is higher from the floor) to the bottom of the heater.

In shops, offices and other sections of aircraft hangars communicating with aircraft storage or servicing areas, heaters shall be installed not less than 8' (2.4 m) above the floor.

Suspended or elevated heaters shall be so located in all spaces of aircraft hangars that they shall not be subject to injury by aircraft, cranes, movable scaffolding or other objects. Provisions shall be made to assure accessibility to suspended heaters for recurrent maintenance purposes.

4.3 Parking Structures and Repair Garages

Installation in garages must be in accordance with the following codes:

United States: Standard for Parking Structures NFPA 88A - latest revision or the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision. Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.

In accordance with the Standard for Parking Structures NFPA 88A, heaters must be located a minimum of 18" (50 cm) below the floor-ceiling assembly or 18" (50 cm) above the floor.

In accordance with the Code for Motor Fuel Dispensing Facilities and Repair Garages, NFPA 30A - latest revision, heaters must not be installed less than 8' (2.4 m) above the floor.

4.4 Electrical

The heater must be electrically grounded in accordance with the following codes:

United States: Refer to National Electrical Code®, NFPA 70 - latest revision. Wiring must conform to the most current National Electrical Code®, local ordinances and any special diagrams furnished.

Canada: Refer to Canadian Electrical Code, CSA C22.1 Part 1 - latest revision.

4.5 Venting

The venting must be installed in accordance with the requirements within this manual and the following codes:

United States: Refer to NFPA 54/ANSI Z223.1 - latest revision, National Fuel Gas Code.

Canada: Refer to CSA B149.1 Natural Gas and Propane Installation Code.

4.6 High Altitude

These heaters are approved for installations up to 2000' (610 m). In USA, consult factory if heater is to be installed above 2000' (610 m). In Canada, high altitude conversion kits are available for installations up to 4500' (1370 m). Installations above 4500' (1370 m) in Canada is by local or provincial authority.

5

Image 11
Contents Combat Page Roberts-Gordon LLC Page Table of Figures Page Manpower Requirements Heater SafetyNational Standards and Applicable Codes Installer ResponsibilityWall Tag Corrosive ChemicalsClearances to Combustibles Minimum Required Installation ClearancesSeparated Combustion Installation Critical Considerations 3.1 Basic InformationInstallation Clearances and Clearances to Combustibles National Standards and Applicable Codes Suspension Major Components 5.1 GeneralCanadian Requirements Vent InstallationVenting 6.1 Venting United States RequirementsVertical Venting Separated Combustion Heaters Models Uhas 150Unvented Operation Horizontal VentingVent and Roof Detail Vent MaterialStandard Vented Heater Common Vertical Vent Termination Concentric Vent Box Horizontal Outside Combustion Air Supply Unvented InstallationAIR Supply Building VentilationConnections GAS PipingFan Control WiringLow Voltage Thermostat with One Heater Positioning ThermostatsGAS Valve Uhas Series Internal Wiring DiagramUhas Series Ladder Wiring Diagram Electrical Connection to the Heater Mechanical Checks Operation and MaintenanceLouvers Electrical ChecksAutomatic Burner Control Sequence Complete the Start-Up Pressure SwitchCheck Gas Rate Turning Off the HeaterLighting Instructions 11.3.1 To Turn On Heater Simple TroubleshootingSimple Troubleshooting Burner Fault Heater OperationUser Instructions Gas Valve Maintenance Burner Maintenance12.3 Fan/Motor Assembly Maintenance Heat Exchanger MaintenanceObjects Maintenance ChecklistVicinity of the Heater Vehicles and OtherFlue Blower Scroll, Wheel When installedBurner Observation WindowTroubleshooting 13.1 General Result in death or electrical shock Troubleshooting For Automatic Ignition Burner SystemsTroubleshooting for Flame Supervision System Conduct start-up procedure as shown on Page 19, Section Troubleshooting for Gas ValvesTroubleshooting for Flue Blower Burner Components Replacement PartsBurner Injectors Burner CompartmentDescription Part Number Ignition Electrode and Flame ProbeLouvers and Louver Spring ExchangerAssemblyUhas Ignition Control Axial Fan/Guard/Motor AssemblyLimit Switches Removal and Replacement Fan Removal and ReplacementTo Replace the Fan Assembly Standard Models 150 400 Uhas Series Dimension Data SpecificationsTechnical Data Table All Models General Technical Data Table All ModelsPage Limitations on Authority Representatives Warranty is Void ifROBERTS-GORDON will PAY for ROBERTS-GORDON will not PAY forPage Page Page Page Fire Hazard
Related manuals
Manual 62 pages 5.65 Kb Manual 48 pages 52.86 Kb

225 250, 175, 300, 400, 150 specifications

Roberts Gorden is a recognized leader in the field of heating solutions, particularly renowned for the development of its innovative radiant heating systems. The lineup of models including the Roberts Gorden 250, 300, 400, 150, and 225 features a blend of advanced technology, exceptional efficiency, and versatile applications that cater to various industrial and commercial needs.

At the core of Roberts Gorden products is their radiant heating technology. Unlike conventional heating systems that warm the air, radiant heaters emit infrared radiation, which directly heats objects and people within a space. This method not only provides a comfortable environment but also reduces energy consumption and minimizes the loss of heat, making it an environmentally friendly choice.

The Roberts Gorden 250 model is specifically designed for smaller spaces, offering compact efficiency without sacrificing power. It features an adjustable output, allowing for tailored heating based on specific requirements. The advanced burner technology ensures optimum combustion efficiency, translating to cost savings on fuel consumption.

Moving on to the Roberts Gorden 300, this unit is well-suited for medium-sized facilities. With enhanced capabilities, the 300 model offers improved heating distribution, making it ideal for warehouses and production floors. The ease of installation and maintenance further enhances its appeal, allowing businesses to focus on their operations rather than on complicated heating systems.

The Roberts Gorden 400 is a powerhouse in the lineup, engineered for larger spaces that demand high-performance heating. Its robust construction and powerful output provide effective warmth even in challenging environments. The unit is equipped with sophisticated controls that promote energy efficiency while maintaining optimum comfort levels.

In the mid-range spectrum, the Roberts Gorden 150 and 225 models cater to businesses needing versatile heating solutions. Both models are designed with user-friendly interfaces and include safety features that comply with industry standards. Their lightweight design allows for easy installation and mobility, making them suitable for temporary or permanent heating applications.

Overall, Roberts Gorden's commitment to innovation and efficiency is evident across its product range. With a focus on sustainability and advanced heating technologies, the Roberts Gorden 250, 300, 400, 150, and 225 models provide reliable heating solutions that meet the diverse preferences of industrial and commercial users. These products are not just about warmth; they are about creating a comfortable and productive environment while minimizing energy costs and environmental impact.