SECTION 13: TROUBLESHOOTING

SECTION 13: TROUBLESHOOTING 13.1 General

WARNING

Explosion Hazard

Installation must be done by a registered installer/ contractor qualified in the installation and service of gas-fired heating equipment or your gas supplier.

Failure to follow these instructions can result in death, injury or property damage.

START

Are gas & electrical

supplies on?

Yes

Does axial fan run

immediately upon supplying

power to heater?

No

Is ignition control showing a

"2 flashes" led code?

No

Does the flue

blower run?

Yess

No

Yes

Yes

No

Turn on supplies.

Wait 10-15 minutes for

limit switch to cool. Does Yes fan stop running?

No

Replace temperature

limit switch.

Burner has locked out due

to ignition failure. Use

Troubleshooting for

Automatic Ignition Burner Systems section to test burner.

Use Troubleshooting for

Flue Blower section to test

fan.

Fan and limit switch are operating normally.

With external controls (i.e.

 

Has burner “Locked Out”? No

thermostat) on, does the No

burner continue through the

 

 

heating cycle?

 

 

 

 

Yes

 

 

Use Troubleshooting for

 

 

Automatic Ignition Burner

 

 

Systems section to test burner.

Yes

 

 

Heater Operating

 

If problems persist, contact

No

Roberts-Gordon LLC at

TROUBLESHOOT ENDS.

www.rg-inc.com

 

The limit switch has

 

tripped. See Manual Reset No

Replace limit switch.

Limit Switch Figure.

 

Yes

Ensure proper air flow clearance for axial fan. Open louvers slightly.

Replace axial fan if it does

not operate.

27

Image 33
Contents Combat Page Roberts-Gordon LLC Page Table of Figures Page Manpower Requirements Heater SafetyWall Tag Installer ResponsibilityCorrosive Chemicals National Standards and Applicable CodesSeparated Combustion Installation Minimum Required Installation ClearancesCritical Considerations 3.1 Basic Information Clearances to CombustiblesInstallation Clearances and Clearances to Combustibles National Standards and Applicable Codes Suspension Major Components 5.1 GeneralVenting 6.1 Venting Vent InstallationUnited States Requirements Canadian RequirementsUnvented Operation Separated Combustion Heaters Models Uhas 150Horizontal Venting Vertical VentingVent and Roof Detail Vent MaterialStandard Vented Heater Common Vertical Vent Termination Concentric Vent Box Horizontal AIR Supply Unvented InstallationBuilding Ventilation Outside Combustion Air SupplyConnections GAS PipingLow Voltage Thermostat with One Heater WiringPositioning Thermostats Fan ControlGAS Valve Uhas Series Internal Wiring DiagramUhas Series Ladder Wiring Diagram Electrical Connection to the Heater Louvers Operation and MaintenanceElectrical Checks Mechanical ChecksAutomatic Burner Control Sequence Check Gas Rate Pressure SwitchTurning Off the Heater Complete the Start-UpSimple Troubleshooting Burner Fault Simple TroubleshootingHeater Operation Lighting Instructions 11.3.1 To Turn On HeaterUser Instructions 12.3 Fan/Motor Assembly Maintenance Burner MaintenanceHeat Exchanger Maintenance Gas Valve MaintenanceVicinity of the Heater Maintenance ChecklistVehicles and Other ObjectsBurner Observation When installedWindow Flue Blower Scroll, WheelTroubleshooting 13.1 General Result in death or electrical shock Troubleshooting For Automatic Ignition Burner SystemsTroubleshooting for Flame Supervision System Troubleshooting for Gas Valves Troubleshooting for Flue BlowerConduct start-up procedure as shown on Page 19, Section Burner Components Replacement PartsBurner Injectors Burner CompartmentDescription Part Number Ignition Electrode and Flame ProbeLouvers and Louver Spring ExchangerAssemblyUhas Ignition Control Axial Fan/Guard/Motor AssemblyFan Removal and Replacement To Replace the Fan AssemblyLimit Switches Removal and Replacement Standard Models 150 400 Uhas Series Dimension Data SpecificationsTechnical Data Table All Models General Technical Data Table All ModelsPage ROBERTS-GORDON will PAY for Warranty is Void ifROBERTS-GORDON will not PAY for Limitations on Authority RepresentativesPage Page Page Page Fire Hazard
Related manuals
Manual 62 pages 5.65 Kb Manual 48 pages 52.86 Kb

225 250, 175, 300, 400, 150 specifications

Roberts Gorden is a recognized leader in the field of heating solutions, particularly renowned for the development of its innovative radiant heating systems. The lineup of models including the Roberts Gorden 250, 300, 400, 150, and 225 features a blend of advanced technology, exceptional efficiency, and versatile applications that cater to various industrial and commercial needs.

At the core of Roberts Gorden products is their radiant heating technology. Unlike conventional heating systems that warm the air, radiant heaters emit infrared radiation, which directly heats objects and people within a space. This method not only provides a comfortable environment but also reduces energy consumption and minimizes the loss of heat, making it an environmentally friendly choice.

The Roberts Gorden 250 model is specifically designed for smaller spaces, offering compact efficiency without sacrificing power. It features an adjustable output, allowing for tailored heating based on specific requirements. The advanced burner technology ensures optimum combustion efficiency, translating to cost savings on fuel consumption.

Moving on to the Roberts Gorden 300, this unit is well-suited for medium-sized facilities. With enhanced capabilities, the 300 model offers improved heating distribution, making it ideal for warehouses and production floors. The ease of installation and maintenance further enhances its appeal, allowing businesses to focus on their operations rather than on complicated heating systems.

The Roberts Gorden 400 is a powerhouse in the lineup, engineered for larger spaces that demand high-performance heating. Its robust construction and powerful output provide effective warmth even in challenging environments. The unit is equipped with sophisticated controls that promote energy efficiency while maintaining optimum comfort levels.

In the mid-range spectrum, the Roberts Gorden 150 and 225 models cater to businesses needing versatile heating solutions. Both models are designed with user-friendly interfaces and include safety features that comply with industry standards. Their lightweight design allows for easy installation and mobility, making them suitable for temporary or permanent heating applications.

Overall, Roberts Gorden's commitment to innovation and efficiency is evident across its product range. With a focus on sustainability and advanced heating technologies, the Roberts Gorden 250, 300, 400, 150, and 225 models provide reliable heating solutions that meet the diverse preferences of industrial and commercial users. These products are not just about warmth; they are about creating a comfortable and productive environment while minimizing energy costs and environmental impact.