TROUBLESHOOTING
If you are having problems with this unit, refer to these troubleshooting hints. Also, refer to the connection diagram to ensure your devices are connected properly.
Problem | Suggested Action |
I have no lights and no function at all.
The fuse continues to blow.
My CO2 outlet never comes on.
The fans are running so often, the CO2 is hardly ever ON.
My CO2 consumption seems to be quite high.
The CO2 level “overshoots” the PPM- 1c set point considerably.
The Hydro pumps are not cycling properly.
Check the fuse and main power. Replace the fuse if required with the correct rated fuse.
Check the equipment connected to the
If the fuse blows repeatedly, verify the devices connected to the unit are working properly and that they are not too large for the
You may need to consider using expansion modules, (UPM / HPR / MLC) to decrease the amperage (load) on the
Verify the
If the Exhaust outlet is ON, the CO2 will not be allowed to run. Turn up the Temperature and Humidity to a higher setting.
In order for the CO2 outlet to function, the timeclock must be in “Daytime” mode. The CO2 is only activated when the lights are “ON”.
You may have too much heat building up in your area or too small of an exhaust fan. Reduce the heat sources or increase your fan size.
You may also consider using a
Make sure your area is sealed. You may want to install a motorized damper to seal your exhaust fans when they are “OFF”. Even though the
If you are operating compressed CO2 valves, consider purchasing the optional
Small areas need less “Inject Duration” time than do larger areas. Larger areas need more “Inject
Frequency” time in order to give the CO2 time to “mix” properly with the ambient air and measured by the PPM sensor.
Start with lower CO2 timer settings for small areas and increase the timer settings for larger ones.
The Hydro pump outlets can be operated
MAKING CONNECTIONS
All of the main functions controlled by the
We highly recommend using only
Page 9