Athena Technologies 6050 instruction manual Manual, Athena, Specifications

Page 2

 

 

 

 

INSTRUCTION

MANUAL

 

 

 

 

ATHENA 6050

 

 

 

 

Automatic

Tuning

 

 

 

 

Temperature

Controller

SPECIFICATIONS:

 

 

 

Inputs:

 

 

 

 

 

Line Voltage

120/240 Vac +lO%, -15%, 50, 60 Hz

Sensor

 

 

 

Thermocouple

Power

Consumption

Less than 6 VA (Instrument)

Ranges

Available

J Couple 0-1400°F (O-760°C)

 

 

 

 

K Couple 0-2500°F (O-137O°C)

Accuracy:

 

 

0.2%

of

full scale

Temperature

Stability

5 m V/°C Max 3m V/°C typ.

Cold end

tracking

0.05°C/°C ambient

Operating

ambient for

 

 

 

rated

accuracy

0 to 55°C

Maximum T/C

lead

 

 

 

resistance for

 

 

 

rated

accuracy

100 Ohm

 

Series

mode

noise

 

 

 

rejection:

 

80 dB

 

 

Common

mode

noise

 

 

 

rejection

 

 

120 dB

 

T/C break

protection:

Upscale

standard

Dual display:

Process

temperature displayed

 

 

 

 

continuously; set point or other

 

 

 

 

parameters updated on lower display.

1

Image 2
Contents Thenil Athena SpecificationsManual Page Page Front Panel Aojustments For Optimum Results with the AUTO-TUNE ModelConfiguration GeneralPage Page CELSIUS/FAHRENHEIT Display Section Internal SwitchesWiring Thermocouple Circuits Standard Thermocouples A. Type Materials Color CodeThermocouple Placement Operating Instructions Page Trouble Shooting Warranty DTHENd